Goodrive35 inverters
Set value
Traverse reset (return to
27
the middle frequency)
28
Counter reset
29
Torque control disabling
30
ACC/DEC disabling
31
Counter trigging
32
Length reset
33
increasing/decreasing
setting temporal clear
34
Switch between motor1
35
Switch commands to
36
Switch commands to
37
Switch commands to
38
communication
39
Pre-excitation commands
40
Power consumption clear
Power consumption
41
42
Keypad setting of the
Function
The setting frequency of the inverter will come back to the
middle frequency.
Counter clear
The inverter shifts from torque control mode to speed
control mode.
Ensure the inverter will not be affected by the external
signals (except for the stopping command) and keep the
current output frequency.
Enable the pulse counter.
Length counter clear
When the terminal closes, the frequency set by UP/DOWN
Frequency
can be cleared. All set frequency will be restored into the
given frequency by the frequency command channel and
the frequency will come back to the value after the
frequency increasing or decreasing.
DC brake
The inverter will begin DC brake after valid command.
Motor-shifting can be controlled after terminal is valid.
and motor2
After the function terminal become valid, the running
command channel will be shifted into keypad running
command channel and the running command channel will
keypad
come back to the original state if the function terminal is
invalid.
After the function terminal become valid, the running
command channel will be shifted into terminal running
command channel and the running command channel will
terminals
come back to the original state if the function terminal is
invalid.
After the function terminal become valid, the running
command channel will be shifted into communication
running command channel and the running command
channel will come back to the original state if the function
terminal is invalid.
Perform pre-exciting if the terminal is valid until the
terminal is invalid.
The power consumption will be cleared after the command
is valid.
If the command is valid, the current running of the inverter
retention
will not affect its power consumption.
The upper limit is set by the keypad if the command is
Instructions
163
Basic operation instruction