Goodrive35 inverters
Function
Name
code
Motor parameter
P00.15
autotuning
AVR function
P00.16
selection
P00.17
Reserved
Function
P00.18
restore parameter
P01 Group Start-up and stop control
P01.00
Start mode
Detailed instruction of parameters
frequency, the inverter needs to derate 10% for each
additional 1k carrier frequency.
Setting range: 1.2 – 15.0 kHz
0: No operation
1: Rotation autotuning
Comprehensive motor parameter autotune
It is recommended to use rotation autotuning when
high control accuracy is needed.
2: Static autotuning 1 (autotune totally); It is suitable
in the cases when the motor cannot de-couple from
the load. The autotuning for the motor parameter will
impact the control accuracy.
3: Static autotuning 2 (autotune part parameters);
when the current motor is motor 1, autotune P02.06,
P02.07, P02.08; and when the current motor is motor
2, autotune P12.06, P12.07, P12.08.
0: Invalid
1: Valid during the whole procedure
The auto-adjusting function of the inverter can cancel
the impact on the output voltage of the inverter
because of the bus voltage fluctuation.
Reserved
0: No operation
1: Restore the default value
2: Cancel the fault record
Note: The function code will restore to 0 after
finishing the operation of the selected function code.
Restoring to the default value will cancel the user
password, please use this function with caution.
0: Start-up directly: start from the starting frequency
P01.01
1: Start-up after DC brake: start the motor from the
starting frequency after DC brake (set the parameter
P01.03 and P01.04). It is suitable in the cases where
reverse rotation may occur to the low inertia load
during starting.
2: Start-up after speed tracing: start the rotating
motor smoothly after tracking the rotation speed and
50
Function parameters
Default
Mod
value
ify
◎
0
○
1
◎
0
◎
0
◎
0