Communication Profile Area (1000 - ABB FCAN-01 User Manual

Canopen adapter module
Table of Contents

Advertisement

112
Communication profile area (1000...1FFF)
Index
Sub-
Name
(hex)
index
1000
0
Device Type
1001
0
Error Register
Communication
Attri-
Type
bute
U32
RO
Describes the type of the device.
U8
RO
Error register for the FCAN-01. Bit
encoded according to DS 301/401. Bit
value 1 = error occurred.
Information
Bit
Description
0
Generic error
1
Current
2
Voltage
3
Temperature
4
Communication error
5
Device-profile-specific
6
Reserved
7
Manufacturer-specific