Modes Of Operation; Homing Mode - ABB FCAN-01 User Manual

Canopen adapter module
Table of Contents

Advertisement

Modes of operation

The operation mode defines the behaviour of the drive. DSP 402
defines following operation modes:

Homing mode

• Profile position mode
• Interpolated position mode
• Profile velocity mode
• Profile torque mode
• Velocity mode
FCAN-01 supports minimal implementation of the operation
modes. Operation mode support is drive-specific (see figure 1).
Interpolated position mode is not supported.
In this chapter scalings of the reference and actual values are
described for each operation mode. Operation-mode-specific
objects are defined in the
111.
In ACSM1, the mode of operation is automatically selected
according to the control mode configured with parameter 34.03
EXT1 CTRL MODE, 34.04 EXT1 CTRL MODE2 or 34.05 EXT2
CTRL MODE1 (depending on the current control location). The
correct reference scaling must be selected with par. 50.04 FBA
REF1 MODESEL.
If the value of parameter 50.04 FBA REF1 MODESEL and 50.05
FBA REF2 MODESEL of ACSM1 is (5) AUTO, it is possible to set
the mode of operation with object 6060h. For more information,
see
Standardised device profile area DSP 402
Homing mode
Homing mode describes various methods of finding a home
position, or zero point. Either limit switches at the ends of travel or
a home switch in mid travel are used. Most of the methods also
use the index (zero) pulse from an incremental encoder. For more
CANopen Object Dictionary
on page
(6000...9FFF).