Standardised Device Profile Area Dsp 402 (6000 - ABB FCAN-01 User Manual

Canopen adapter module
Table of Contents

Advertisement

124
Standardised device profile area DSP 402 (6000...9FFF)
Index
Sub
Access
603Fh
RO
6040h
RW
6041h
RO
6042h
RW
6043h
RO
6044h
RO
6046h
0
RO
1
RW
2
RW
6048h
0
RO
1
RW
2
RW
6049h
0
RO
1
RW
2
RW
Communication
Type
Name
U16
Error code
U16
Control word
U16
Status word
INT16
Target velocity
INT16
Vl velocity demand
INT16
Vl control effort
Vl velocity min max
amount
U8
Number of entries
U32
Vl velocity min
amount
U32
Vl velocity max
amount
Vl velocity
acceleration
U8
Number of entries
U32
Delta speed
U16
Delta time
Vl velocity decelera-
tion
U8
Number of entries
U32
Delta speed
U16
Delta time
Information
See chapter
CANopen error
codes
on page 133.
See chapter
Communication profiles
on
page 69.
Instantaneous velocity provided
by the ramp function. Scaled to
the unit of the vl target velocity.
See chapter
Communication profiles
on
page 69.
Vl velocity min max amount
Default: 2
Mapped internally to vl velocity
min pos and vl velocity max neg
values
Mapped internally to vl velocity
max pos and vl velocity max neg
values
Slope of the acceleration ramp =
delta speed / delta time. If delta
time = 0, function follows the
setpoint (=target velocity) value
Default: 2
[rpm]
0...65536 [sec]
Slope of the deceleration ramp =
delta speed / delta time. If delta
time = 0, function follows the
setpoint (=target velocity) value
Default: 2
[rpm]
0...65536 [sec]
Support
a
h
p
i
p
p
v
l
m
p
p
v
t
l
l
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x

Advertisement

Table of Contents
loading

Table of Contents