ABB FCAN-01 User Manual page 102

Canopen adapter module
Table of Contents

Advertisement

102
Write the CANopen objects via the CAN bus as shown in the
following table. The FCAN-01 module must be in the Pre-
operational state.
Object
Sub-
index
index
1400
01
1400
02
1600
00
1600
01
1600
02
1600
00
1400
01
1800
01
1800
02
1800
05
1A00
00
1A00
01
Communication
Name
Rx PDO1 Parameter,
COB-ID
Rx PDO1 Parameter,
Transmission type
Rx PDO1 Mapping,
Number of entries
Rx PDO1 Mapping,
Mapped object 1
Rx PDO1 Mapping,
Mapped object 2
Rx PDO1 Mapping,
Number of entries
Rx PDO1 Parameter,
COB-ID
Tx PDO1 Parameter,
COB-ID
Tx PDO1 Parameter,
Transmission type
Tx PDO1 Parameter,
Event timer
Tx PDO1 Mapping,
Number of entries
Tx PDO1 Mapping,
Mapped object 1
Write
value
(hex)
80000203 Disable Rx PDO1 *
FF
Transmission type 255
0
Required before
mapping **
60400010 6040h Control word
(subindex 0, length 16
bits)
60420010 6042h vl target velocity
(subindex 0, length 16
bits)
2
2 objects mapped **
203
Enable Rx PDO1, use
COB-ID 203h.
80000183 Disable Tx PDO1 *
FF
Transmission type 255
64
100 ms
0
Required before
mapping **
60410010 6041h Status word
(subindex 0, length 16
bits)
Description