Abort Sdo Transfer; Abort Sdo Transfer Protocol - ABB FCAN-01 User Manual

Canopen adapter module
Table of Contents

Advertisement

108

Abort SDO Transfer

Abort SDO Transfer Protocol

This protocol is used to implement the Abort SDO Transfer
Service.
Client/Server
Request
cs
Command specifier; cs = 4: Abort transfer request.
x
Not used. The value is always 0.
m
Multiplexor; Represents the index and subindex of the SDO.
d
Contains a 4 byte abort code which includes the reason for the abort.
Communication
Abort SDO Transfer
0
1
7...5
4...0
cs = 4
x
4
d
m
Server/Client
8