AC and DC parameters for the CANopen network
Bus cable and termination resistors
The cables, connectors, and termination resistors used in
CANopen networks must meet the requirements specified in
ISO 11898.
The table below lists the standard values for DC parameters for
CANopen networks with less than 64 nodes:
Bus
length
Length-related
[m]
resistance [mohm/m]
0...40
40...300
300...600
600...1000
*
Recommended cable for AC parameters: 120 ohm impedance and 5 ns/m line
delay.
With drop cables the recommended cable cross-section is
0.25...0.34 mm
Electrical installation
*
Bus cable
Cross-section
70
< 60
< 40
< 26
2
.
Termination
resistance
2
[mm
]
0.25...0.34
0.34...0.6
150...300
0.5...0.6
150...300
0.75...0.8
150...300
Baudrate
[kbit/s]
[ohm]
124
1000 at 40 m
> 500 at 100 m
> 100 at 500 m
> 50 at 1 km