How To Power Up A T1100 As Unit In An Ac Environment; How To Change Passwords - Tekelec 1100 Hardware Manual

Application server
Hide thumbs Also See for 1100:
Table of Contents

Advertisement

To power up an added server, turn ON (flip the switch toward the | indicator) the
breakers that correspond to the position where the server was added, as shown in
BreakerSettings.pdf. Next, turn ON the power switch on the front of the T1100
chassis.

How to Power Up a T1100 AS Unit in an AC Environment

Use the following procedure to power up a T1100 AS unit in an AC environment.
WARNING: Before powering up, verify that all output breakers or power
distribution unit switches are set to the OFF (O) position. Be sure the chassis
power switch is set to the OFF position.
Procedure 6-8.
1.
Ensure that all AC and DC connections have been secured and checked.
2.
Verify the ground at the AC outlet. See "How to Verify the Ground in an AC
Environment" on page 6-13.
3.
Set the output breakers to "ON" to send power to the T1100 AS unit.
4.
Turn the T1100 AS chassis switch to "ON".
5.
This procedure is complete.

How to Change Passwords

For security purposes, Tekelec recommends that all default passwords be
changed to your own passwords. The new passwords should be kept in a secure
location.
• To change the passwords for the T1100 AS platforms, refer to the application
manual for the application loaded on each server.
• To change the passwords for the Ethernet switches, refer to the application
manual for the application loaded on each server.
NOTE: There should always be a person on-site who knows the new
passwords. If there is a need to contact the Customer Care Center, please
provide the passwords on request.
6-16
Preliminary
Power Up T1100 AS Unit in an AC Environment
Post Installation Procedures
910-2969-001 Revision H, February 2007