CAUTION: A readily accessible disconnect device that is suitable, approved,
and rated shall be incorporated in the field wiring.
CAUTION: Connect to a reliably grounded SELV source which is reliably
earthed and electrically isolated from the AC source.
CAUTION: Use only listed closed loop connectors for connection to the
supply.
CAUTION: When some CPCI cards arrive from the manufacturer, they may
have a small plastic cover over the screws and/or the alignment ejector pins.
Remove and discard these plastic covers. If inserting the cards takes an
excessive amount of force, check for obstructions. Forcing the card into a slot
may damage the ejector handle or pin.
NOTE: Use a minimum of 26 AWG telecommunications line cord for
connection to the modem.
Regulatory Compliance and Certification
Tekelec products are tested to meet the following regulatory standards:
• Network Equipment Building System (NEBS) level 3 as listed in Telcordia
SR-3580.
• Applicable Telcordia Electromagnetic Compatibility and Electrical Safety
requirements in GR-1089-CORE.
• Applicable Physical Protection requirements in GR-63-CORE.
• Relevant directives and harmonized standards in support of the products
Compliance European (CE) mark required in Europe. Figure 2-1 shows the
mark used to indicate this compliance.
Figure 2-1. European Directives CE Mark
2-4
Safety and Pre-Installation Requirements
Preliminary
910-2969-001 Revision H, February 2007