Post Installation Procedures
Check When Done

How to Power Up

WARNING: Only a certified Tekelec test engineer should power up a system after
installation.
To power up, set the appropriate breakers to the ON position as described in one of the following
sections.
How to Power Up a Heavy Duty Frame
How to Power Up AddedT1100 AS Unit in DC Environment

How to Power Up a T1100 AS Unit in an AC Environment

Turn the switch on the front of the T1100 AS to ON. When the breakers that supply power to the
T1100 AS unit are switched ON, and the chassis switch is turned ON, the unit will execute a power
up sequence which includes a Power On Self Test (POST). For information about initializing the
software that runs onT1100 AS chassis, refer to the application manuals included with your
documentation.
How to Power Up a Heavy Duty Frame
In a Direct Current (DC) environment, to power up the equipment installed in the heavy duty
frame, turn ON (flip the switch toward the | indicator) all the breakers that correspond to servers
in the frame, as shown in BreakerSettings.pdf. Next, turn ON the power switch on the front of
theT1100chassis.
How to Power Up AddedT1100 AS Unit in DC Environment
WARNING: Before powering up a server that has been added to an existing frame
in a DC environment, verify that the breakers that correspond to the position where
the server has been added are set to the OFF (O) position. Then, be sure that the
chassis switch is set to the OFF position.
To power up an added server, turn ON (flip the switch toward the | indicator) the breakers that
correspond to the position where the server was added, as shown in BreakerSettings.pdf. Next, turn
ON the power switch on the front of the T1100 chassis.
How to Power Up a T1100 AS Unit in an AC Environment
Use the following procedure to power up a T1100 AS unit in an AC environment.
96
Customer site survey book is signed off.
Check that power coming into the frame is -48V
+/- 6V before powering up the frame.
on page 96
on page 96
on page 96
910-2969-001 Revision K, June 2009
Hardware Manual
Verify that:

Advertisement