Table 2-1. Space Requirements - Tekelec 1100 Hardware Manual

Application server
Hide thumbs Also See for 1100:
Table of Contents

Advertisement

Earthquake Resistance
All Tekelec system configurations are designed to assure that the system remains
operational during and after an earthquake, even when the system is located on
the upper floors of a zone 4 central office.
Space Requirements
Provide space as described in Table 2-1. These space requirements provide for
Tekelec equipment installed in a 23-inch heavy-duty frame, which measures 7 feet
high. Separator panels and end panels add to the width of multiple frame
systems.
Table 2-1.
Building Area
Halls
Frame location
Side aisles
Front and rear
access
Side access
In addition, when planning the installation, be sure to take into account spare
hardware storage, modems, terminals, printers, cross connect panels, and all
other items that might require space in a system.
2-8
Preliminary
Space Requirements
Dimensions
4.5 feet wide by 8
feet tall
(1.4 meters wide
by 2.4 meters tall)
30 inches wide by
24 inches deep
(76.2 cm wide by
60.96 cm deep)
4 feet (1.2 meters) To allow maneuvering frames into
3 feet 6 inches
(107 cm)
12 inches (31 cm)
Safety and Pre-Installation Requirements
Notes
To provide a clear, uncluttered route
for moving equipment between the
loading/receiving dock and the
planned system location
Floor area recommended for one
Tekelec frame (multiply by the
number of frames listed on the Initial
Sales Order)
Total area per frame = 720 square
inches (5.0 square feet)
(0.465 square meters)
place and provide ample work space
around the equipment
From walls or other frames
From walls or other frames
910-2969-001 Revision H, February 2007