CAUTION: This equipment has a connection between the earthed conductor
of the DC supply circuit and the earthing conductor.
CAUTION: The Branch Circuit Overcurrent Protection shall be rated
minimum -48V, maximum 40A.
CAUTION: Equipment is to be installed in restricted access areas in
accordance with articles 110-16, 110-17, and 110-18 of the National Electric Code,
ANSI/NFPA 70.
CAUTION: A readily accessible disconnect device that is suitable, approved,
and rated shall be incorporated in the field wiring.
CAUTION: Connect to a reliably grounded SELV source which is reliably
earthed and electrically isolated from the AC source.
CAUTION: Use only listed closed loop connectors for connection to the
supply.
CAUTION: When some CPCI cards arrive from the manufacturer, they may
have a small plastic cover over the screws and/or the alignment ejector pins.
Remove and discard these plastic covers. If inserting the cards takes an
excessive amount of force, check for obstructions. Forcing the card into a slot
may damage the ejector handle or pin.

T1100 AS Hardware System FRUs and Part Numbers

The following T1100 AS hardware system components can be replaced in the
field:
• Air filters (rectangular filter P/N 551-0022-03 and square filter P/N
551-0022-02)
• Fan assemblies (rectangular fan P/N 840-1125-03 and square fan P/N
840-1133-01).
• SATA hard drives (P/N 870-2787-02)
• Removable media drives assembly (P/N 870-2785-02)
7-4
Preliminary
910-2969-001 Revision H, February 2007
Field Replaceable Units