Attach the ground cable (P/N 830-0977-01) to the server. The ground cable
has a different lug at each end and will terminate only one way.
3.
Tighten the nuts to secure the cable to the rear of the T1100 AS.
4.
Connect the other end of the cable to the side of the frame nearest the T1100
AS chassis (see Figure 6-2 on page 6-6). Be sure that the T1100 AS can slide in
and out on its rails without binding this cable.
5.
This procedure is complete.
Next, go to Procedure 6-4, "Connect Logic Ground from Logic Ground Terminal
Strip to Ground Window," on page 6-9.
How to Ground the Logic Connector in a DC Environment
This section describes how to attach the logic ground cables to the logic connector
at the back of the server.
The logic ground cables are a part of the internal power distribution. They
provide a ground connection between each server and the main ground. The logic
ground is connected from each server to the terminal strip and from the terminal
strip to the system bar or to the ground window by the consolidated power
cables, cable #6 AWG (P/N 690-0131-01), terminal lug (P/N 804-0817-R02), and
heat-shrink (P/N 804-0228-R01).
To complete the logic ground, both of the following procedures must be
performed:
• Attach the logic ground from the logic ground terminal block to the system
bar (EF00) or to the isolated ground of the Ground Window (Procedure 6-4 on
page 6-9).
WARNING: Be sure that there is no connection between Tekelec
equipment logic ground and the logic ground of any other
telecommunications equipment.
• Attach the logic ground cable from the logic ground port on the T1100 AS to
the logic ground screws on the logic ground terminal block (Procedure 6-5 on
page 6-11).