Table 5: Space Requirements - Tekelec 1100 Hardware Manual

Application server
Hide thumbs Also See for 1100:
Table of Contents

Advertisement

Safety and Pre-Installation Requirements
Maximum: 4000 meters above sea level at ambient temperature of 40˚ C (104˚ F)
HVAC Requirements
Tekelec products are designed to bring cool air in from the bottom front and exit heated air out
the top rear of the installed equipment.
The required HVAC (Heating, Ventilation, and Air Conditioning) capacity depends on the installed
equipment. To calculate needed HVAC capacity, determine the total wattage of the installed
equipment and use the following formula:
BTUs/hr. =
watts x 3.413
The amount of power required by frame components is found at: PowerReqmts.pdf.
Lighting
Adequate lighting should be provided in the room where the equipment is to be located. Lighting
fixtures must be far enough from the equipment and cables to prevent heat damage and to allow
safe access to equipment and cables.
Earthquake Resistance
All Tekelec system configurations are designed to assure that the system remains operational
during and after an earthquake, even when the system is located on the upper floors of a zone 4
central office.
Space Requirements
Provide space as described in
provide for Tekelec equipment installed in a 23-inch heavy-duty frame, which measures 7 feet
high. Separator panels and end panels add to the width of multiple frame systems.

Table 5: Space Requirements

Building Area
Halls
Frame location
34
Table 5: Space Requirements
Dimensions
4.5 feet wide by 8 feet tall
(1.4 meters wide by 2.4 meters
tall)
30 inches wide by 24 inches
deep
(76.2 cm wide by 60.96 cm
deep)
Hardware Manual
on page 34. These space requirements
Notes
To provide a clear, uncluttered
route for moving equipment
between the loading/receiving
dock and the planned system
location
Floor area recommended for
one Tekelec frame (multiply by
the number of frames listed on
the Initial Sales Order)
Total area per frame = 720
square inches (5.0 square feet)
(0.465 square meters)
910-2969-001 Revision K, June 2009

Advertisement

Table of Contents
loading