Bfm#126: Upper/Lower Error Status Data Automatic Transfer-To Data Register Specification - Mitsubishi Electric MELSEC-FX3S Series Manual

Table of Contents

Advertisement

FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
FX
-4AD/FX
-4AD (4-channel Analog Input)
3U
3UC
3. Caution regarding EEPROM writing
If data is written to BFM#0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
5.4.22 BFM#126: Upper/lower error status data automatic transfer-to data register
specification
Use this function to automatically transfer the upper/lower limit error status data (BFM#26) to the data register
specified in BFM#126.
When the upper/lower limit error is detected, data will be automatically transferred from the 4AD to the PLC.
For this reason, the PLC does not need any program for reading the data, and the scanning time of the PLC
can be shortened.
1. If "BFM#126 = K208 (initial value)"
Specified data register
D208
2. Cautions regarding upper/lower limit error status data automatic transfer-to data register
specification
• If a data register is already specified for the other automatic transfer functions, do not specify the same
data register.
• Be sure to turn on the upper/lower limit error status data automatic transfer function (b5 of BFM#22) and
the upper/lower limit detection function (b1 of BFM#22).
• The data written to BFM#126 will be retained in the EEPROM.
3. Caution regarding EEPROM writing
If data is written to BFM#0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.
PLC User's Manual - Analog Control Edition
→ For a detailed description of the upper/lower limit error status data (BFM#26),
Description
Upper/lower limit error status data in BFM#26
5 Buffer Memory (BFM)
5.4 Buffer Memory Details
Setting range: 0 to 7999
Initial value (at delivery) : K208
Numeric data type: Decimal (K)
refer to Subsection 5.4.9.