Example Of Changing Parameters On 3-Tier System (When Only The First Half Of Link Parameter Is Set) - Mitsubishi Electric MELSEC-A Series Manual

Network modules
Hide thumbs Also See for MELSEC-A Series:
Table of Contents

Advertisement

2
REPLACEMENT OF MELSECNET (II) AND /B (PLC TO PLC NETWORK)
2.5.3 Example of changing parameters on 3-tier system (When only the first half of
link parameter is set)
The following shows how to change a system on which first half of LB/LW link parameters is set, when
replacing the MELSECNET (II) 3-tier system with MELSECNET/H. Network range assignment of the
present MELSECNET (II) 3-tier system can be used in replacement with MELSECNET/H.
The MELSECNET (II) 2-tier is replaced with the network 1 of MELSECNET/H, and 3-tier is replaced with
the network 2. The MELSECNET (II) master station is replaced with the MELSECNET/H control station,
and MELSECNET local stations are replaced with MELSECNET/H normal stations.
Optical loop
Link parameter of 2-tier
Link parameter of 3-tier
master station (L1/m)
Step 1: Control station (1Mp3) setting
Replace the link parameter setting of MELSECNET (II) 2-tier master station directly with "Network range assignment (Common
parameters)" of MELSECNET/H network 1 control station 1Mp3.
Step 2: Gateway station (1Ns1/2Mp3) setting
Data transfer between 2 and 3-tier, performed automatically on MELSECNET (II), should be set with parameter setting on
MELSECNET/H. Perform the following settings.
• Replace the link parameter setting of MELSECNET (II) 3-tier master station directly with "Network range assignment (Common
parameters)" of MELSECNET/H network 2 control station 2Mp3.
The range assignment should be performed including the same LB/LW size as that of 1Mp3 to relay the network 1 control
station 1Mp3.
• Set "Refresh parameters" not to duplicate B/W of networks 1 and 2 on the CPU.
• Set data transfer between 2 and 3-tier of MELSECNET (II) in "Interlink transmission parameters" between gateway stations
1Ns1 and 2Mp3.
Step 3: Normal station (1Ns2, 2Ns1, 2Ns2) setting
Set "Refresh parameters" of each normal station (1Ns2, 2Ns1, 2Ns2) on MELSECNET/H networks 1 and 2.
2
- 27
MELSECNET ( II )
A3UCPU
A2UCPU
M
MELSECNET (II)
2-tier
A3UCPU
L1/m
MELSECNET (II)
3-tier
l1
A2UCPU
A2UCPU
B/W 0
100
280
380 3FF
M
L1/m
L2
m l1 l2
100
180 200
280
Concept of MELSECNET (II) 3-tier system replacement
Optical loop
Q06UDVCPU
L2
1Mp3
l2
2Ns1
Q02UCPU
.
MELSECNET/H
Q02UCPU
1Ns2
MELSECNET/H
Network 1
Q06UDVCPU
Gateway
1Ns1/2Mp3
station
MELSECNET/H
Network 2
2Ns2
Q02UCPU