Preparing the Library Location for Seismic Areas

Figure 2-2
seismic activity. To meet this requirement, the library must have all four wheel
assemblies removed so that the mounting studs for the wheel assembly can be
used to fix the library in its permanent position.
CAUTION:
Bodily injury/equipment damage: You must consult a seismic engineer
to verify seismic zone exposures and adequate site preparation.
Figure 2-2. Library Floor—Wheel Stud Locations (C67270)
1
2
3
4
5
1. 33.274 mm (1.312 in.)
3. 558.8 mm (22 in.)
5. 33.35 mm (1.313 in.)
7. 85.725 mm (3.375 in.)
9. 1168.7 mm (46 in.)
See
Figure 2-1 on page 2-4
allow for adequate air intake for cooling, adequate cooling clearances around
the library: 150 mm (6 in.) above, 114.3 mm (4.5 in.) below, and 51 mm (2 in.)
on each side, and adequate space for service.
95896
for the locations of the mounting studs for sites within areas of
6
7
and note that the library's permanent position must
Eleventh Edition
StorageTek Proprietary
Preparing the Library Location
8
9
2. 685.8 mm (27 in.)
4. 60.325 mm (2.375 in.)
6. 21.92 mm (0.863 in.)
8. 1039.1 mm (40.91 in.)
10. 21.895 mm (0.86 in.)
10
C67270
2-5