Testing the Subsystem

Before placing the library online, you should run diagnostic tests. StorageTek
suggests running two diagnostic tests from the library's operator panel: Get-Put
and the Mount-Dismount Loop.
You also may run diagnostic tests from a laptop computer connected to either
the SER1 port or CSE port on the electronics module. The laptop baud setting
for the SER1 port is 38400 and for the CSE port 9600 (initially).

Get-Put Loop Diagnostic Test

The Get-Put loop diagnostic test validates cell-to-cell move capabilities by using
a diagnostic cartridge and the swap cell. The robot:
• Retrieves (gets) the diagnostic tape from its storage cell
• Moves the hand and cartridge laterally and vertically
• Places (puts) the cartridge back into its reserved cell
To run the Get-Put diagnostic test:
1. Make sure that the front door is closed and that the library status screen is
displayed on the operator panel.
2. Make sure that there is a diagnostic cartridge in the reserved area.
3. From the status screen, press the
Main Menu will appear.
4. Press the arrow buttons until the cursor highlights DIAGNOSTICS.
5. Press the
6. Press the arrow buttons until the cursor highlights GET-PUT LOOP.
7. Press the
8. Use the up and down arrow buttons to set the number of times you want
the test to run.
9. Press the
You will be prompted to confirm that you want the library in
Mode
Confirm this by pressing the
10. After this diagnostic test runs to completion, press the
return to the main diagnostics menu.
Note: If the diagnostic test fails, a message and an FSC will appear on the
95896
button. The Main Diagnostics Menu will appear.
SELECT
button. The Get-Put Mode screen will appear.
SELECT
button.
SELECT
(offline) before beginning the test (ARE YOU SURE?).
operator panel.
Eleventh Edition
StorageTek Proprietary
button on the operator panel. The
MENU
button.
SELECT

Testing the Subsystem

Maintenance
button to
MENU
6-11