Rack Area

CAUTION:
Potential damage to library electronics and drives: The two perforated
sections in the rear of the rack area provide ventilation for the library
processor, power supply, and drives. Do not block these sections.
Potential equipment damage: The total maximum weight of equipment
installed in this location must not exceed 77.1 kg (170 lb), and the total
height must not exceed 6 units or U's.
The internal 6-unit (U) rack area, behind the top front door, may be used by
customers for additional equipment. Requirements for this area are:
• See
customer understands this information.
• Route power cables through the cutouts in the bottom of the library frame.
See

Power Considerations

In the L180 library, some combinations of input voltage and current, drive type,
and plug type, limit the number of drives that can be installed. See the
following paragraphs for details.

At 120 to 127 VAC

You may install the maximum number of drives in the L180 library if the power
source at the site is 120 to 127 VAC:
• 10 DLTs (with or without Power Factor Correction [PFC])
• 10 LTOs
• 6 StorageTek T9840s and one DLT drive
You may do so even if the library is connected to a single AC circuit.
Note: For partial drive column power redundancy, StorageTek recommends
95896
"Rack Safety and Precautions" on page xxix
Figure 2-1 on page 2-4
connecting the library to a second AC circuit.