BONFIGLIOLI ACTIVE Cube ACU 201-01 Operating Instructions Manual page 255

Frequency inverter 230 v / 400 v 0.25 kw ... 132 kw
Table of Contents

Advertisement

Via parameter
slave drive.
Operation mode
0 - Off
1 - Master Drive
2 - Slave Drive
For traverse mode, the reference value source is selected via parameter
frequency
Traverse mode becomes active as soon as the
the first time. This frequency is reached via the values for
420 and
Deceleration anticlockwise
436 and
Time
The frequency range for shot-effect mode is limited by the
and the
Maximum frequency
During traverse operation, the configured traverse parameter values cannot be
changed.
The source of the handshake signal is selected via
Operating Instructions ACU
06/13
435, the drive is configured as a master drive or
Operation mode
435
48.
Acceleration Anticlockwise
423. In shot-effect mode, the values for
437 are active.
Deceleration Time
419.
Function
The traverse function is deactivated.
Operation as master drive.
Operation as slave drive.
Reference frequency
422 and
Deceleration (clockwise)
Handshake Traverse Function
Reference
48 is reached for
Acceleration (clockwise)
421 and
Acceleration
418
Minimum frequency
49.
255

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACTIVE Cube ACU 201-01 and is the answer not in the manual?

Questions and answers

Владимир
February 17, 2025

Конфигурация 610 контроллером крутящего момента. Опорный крутящий момент представлен в видепроцент и он передается в соответствующие эксплуатационные показателиприложение. Переключение между регулированием переменной скорости и регулированием крутящего моментаУправление осуществляется без рывков во время работ? Как подробнее узнать об этом режиме? Нужно обеспечить останов с заданным моментом на валу мотора

Table of Contents

Save PDF