Stopping behavior 0
Free stopping
Stopping behavior 1
+ Switch off
Stopping behavior 2
Stop + Hold
Stopping behavior 3
Stop + DC brakes
Stopping behavior 4
Emergency stop
+ switch off
Stopping behavior 5
Emergency stop +
Stopping behavior 6
Emergency stop +
Stopping behavior 7
Direct current brake
Please refer to the notes for controlling a mechanical brake in chapter 15.3.5 Brake
release.
For connection of a synchronous motor BONFIGLIOLI VECTRON recommends the
setting of
Operating Instructions ACU
06/13
Stopping Behavior
The inverter is disabled immediately. The drive deener-
gized immediately and coasts freely.
The drive is brought to a standstill at the set decelera-
tion. As soon as the drive is at a standstill, the inverter is
disabled after a after a holding time. The holding time
can be set via the parameter
Stop
Depending on the setting of the parameter
620, the
tion
Starting voltage
holding time.
The drive is brought to a standstill at the set deceleration
and remains permanently supplied with current.
Depending on the setting of the parameter
620, the
tion
standstill or the
In configurations 2xx the magnetizing current is used
instead of the
current results from
Reduction Factor Flux
The drive is brought to a standstill at the set decelera-
tion. As from standstill, the DC set via parameter
current
Comply with the notes in chapter "DC brake".
Stopping behaviors 3, 6 and 7 are only available in the
configurations for V/f sensor-less control (1xx).
The drive is brought to a standstill at the emergency stop
deceleration. As soon as the drive is at a standstill, the
inverter is disabled after a after a holding time.
The holding time can be set via the parameter
638. Depending on the setting of the parameter
time
Starting function
pressed as from standstill or the
applied.
The drive is brought to a standstill at the emergency stop
deceleration and remains permanently supplied with cur-
rent.
Depending on the setting of the parameter
620, the
Hold
tion
standstill or the
The drive is brought to a standstill at the set emergency
stop deceleration. As from standstill, the DC set via pa-
rameter
ing time
Comply with the notes in chapter "DC brake".
Brake
Stopping behaviors 3, 6 and 7 are only available in the
configurations for V/f sensor-less control (1xx).
Direct current braking is activated immediately. The di-
rect current set with the parameter
is impressed for the die
Comply with the notes in chapter "DC brake".
Stopping behaviors 3, 6 and 7 are only available in the
configurations for V/f sensor-less control (1xx).
630 = 22.
Operation Mode
Holding time
623 is impressed or the
Starting current
600 is applied for the duration of the
623 is impressed as from
Starting current
Starting voltage
623. The magnetizing
Starting current
Rated magnetizing current
778.
631 is impressed for the
620, the
Starting current
623 is impressed as from
Starting current
Starting voltage
631 is impressed for the
Braking current
632.
Braking time
638.
Starting func-
Starting func-
600 is applied.
716 and
Braking
632.
Braking time
Holding
623 is im-
600 is
Starting voltage
Starting func-
600 is applied.
Brak-
631
Braking current
632.
139

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACTIVE Cube ACU 201-01 and is the answer not in the manual?

Questions and answers

Владимир
February 17, 2025

Конфигурация 610 контроллером крутящего момента. Опорный крутящий момент представлен в видепроцент и он передается в соответствующие эксплуатационные показателиприложение. Переключение между регулированием переменной скорости и регулированием крутящего моментаУправление осуществляется без рывков во время работ? Как подробнее узнать об этом режиме? Нужно обеспечить останов с заданным моментом на валу мотора

Table of Contents

Save PDF