14.11 PWM-/repetition frequency input

The use of a PWM (pulse-width modulated) frequency signal completes the various
possibilities of the reference value specification. The signal at one of the available
digital inputs is evaluated according to the selected
PWM frequencies in the range between 50 Hz and 150 kHz can be evaluated.
Operation mode
0 - Off
2 - PWM S2IND, 0 - 100%
3 - PWM S3IND, 0 - 100%
6 - PWM S6IND, 0 - 100%
12 - PWM S2IND, -100 - 100%
13 - PWM S3IND, -100 - 100%
16 - PWM S6IND, -100 - 100%
S2IND
21 -
Single evaluation pos.
S2IND
22 -
Double evaluation pos.
S3IND
31 -
Single evaluation pos.
S3IND
32 -
Double evaluation pos.
S6IND
61 -
Single evaluation pos.
S6IND
62 -
Double evaluation pos.
121 to 162
If a digital input is configured as a PWM or repetition frequency input, this input cannot
be used for other functions.
Check the link of the digital inputs to other functions.
170
496
The PWM signal or repetition frequency is zero.
PWM signal capture on terminal X210A.4.
0 ... 100% of
or 0 ... 100% of
PWM signal capture on terminal X210A.5.
0 ... 100% of
or 0 ... 100% of
PWM signal capture on terminal X210B.1.
0 ... 100% of
or 0 ... 100% of
PWM signal capture on terminal X210A.4.
-100 ... 100% of
519 or -100 ... 100% of
PWM signal capture on terminal X210A.5.
-100 ... 100% of
519 or -100 ... 100% of
PWM signal capture on terminal X210B.1.
-100 ... 100% of
519 or -100 ... 100% of
Repetition frequency input on terminal X210A.4.
One edge of the frequency signal is evaluated with
a positive sign.
Repetition frequency input on terminal X210A.4.
Both edges of the frequency signal are evaluated
with a positive sign.
Repetition frequency input on terminal X210A.5.
One edge of the frequency signal is evaluated with
a positive sign.
Repetition frequency input on terminal X210A.5.
Both edges of the frequency signal are evaluated
with a positive sign.
Repetition frequency input on terminal X210B.1.
One edge of the frequency signal is evaluated with
a positive sign.
Repetition frequency input on terminal X210B.1.
Both edges of the frequency signal are evaluated
with a positive sign.
Repetition Frequency Input. Operation modes 21
to 62 with evaluation of the frequency signal, but
with a negative sign.
Operating Instructions ACU
496.
Operation mode
Function
Maximum reference percentage
419.
Maximum frequency
Maximum reference percentage
419.
Maximum frequency
Maximum reference percentage
419.
Maximum frequency
Maximum reference percentage
Maximum frequency
Maximum reference percentage
Maximum frequency
Maximum reference percentage
Maximum frequency
519
519
519
419.
419.
419.
06/13

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ACTIVE Cube ACU 201-01 and is the answer not in the manual?

Questions and answers

Владимир
February 17, 2025

Конфигурация 610 контроллером крутящего момента. Опорный крутящий момент представлен в видепроцент и он передается в соответствующие эксплуатационные показателиприложение. Переключение между регулированием переменной скорости и регулированием крутящего моментаУправление осуществляется без рывков во время работ? Как подробнее узнать об этом режиме? Нужно обеспечить останов с заданным моментом на валу мотора

Table of Contents

Save PDF