Operating Instructions
DeviceNet
Drives Solutions
www.danfoss.com/drives

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT 5000 and is the answer not in the manual?

Questions and answers

Summary of Contents for Danfoss VLT 5000

  • Page 1 ® 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA Operating Instructions DeviceNet Drives Solutions www.danfoss.com/drives...
  • Page 2: Table Of Contents

    Control Word and Status Word under Instance 20/70 ..........20 Programming ....................21 Quick Setup ......................21 Special Attention ....................21 Warning and Alarm Messages ................26 Warning and Alarm Messages ................26 Factory Settings ..................... 27 MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 3: Introduction To Danfoss Vlt Series And Devicenet

    1. Support interger parameters through the dual ported RAM. 2. Manipulate the dual ported RAM parameters to interface with the CAN. 3. Monitor network activity "watchdog" function to determine Master – Slave communication continuity. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 4: Network Variable Handling

    Master/Slave connection set which identifies a use For recoverable errors such as [1] and [2] the option for all group 2 message identifiers. The ability to card shall re-send the watchdog message when MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 5 Group 3 messages allows the option card to also be an Unconnected Explicit Message Manager (UCMM) with the UCMM request and response message identifier. Explicit message connections are unconditionally point-to-point. Point-to-point connections exist between two devices only. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 6: Technical Data

    This object - 11 - 25 VDC is required by all DeviceNet products. - 70 mA draw per VLT 5000 DeviceNet node This object requires no class attributes. Its instance attributes are the following: Vendor...
  • Page 7: Cable Lengths

    @ 80°C Storage temperature -40° to + 85°C Pull tension 190 Ibs max * Other types of jacket insulation are allowable provided that internal construction and electrical charactersitics adhere to this specification. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 8: Cable Cross Section

    ® 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA DeviceNet Cable Cross Section MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 9: Connection Of The Cable Screen

    Strain relief, if required, must be provided by the developer. In current installations of this type of connector, the strain relief is attached to the product. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 10: User Interface

    4. when the LED is flashing red, the network has a connection time-out 5. when the LED is red, the network has a critical link failure. No further direct user interface is considered No further direct user interface is considered. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 11: Understanding Module Configuration Switches

    Dip Switches, you must ensure that each serial device on the network has a unique address. Also, all devices connected to the network must be set at the same baud rate. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 12: Emc Precautions

    DeviceNet network. Additional information on EMC to keep the greatest possible distance between can be found in the VLT 5000 Series Instruction Manual. the cables, especially where cables are running in parallel over long distances.
  • Page 13: Setting The Devicenet Node Address

    Dip switches 7 and 8 set the baud rate at which Baud Rate Switch Setting Switch Setting the Communication Module communicates on the network. The factory default setting is 125K BPS. 125 kBPS 250 kBPS 500 kBPS 125 kBPS MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 14: Vlt Response Time

    The internal update time for 2. The internal update time, which is the time it takes the different types of data are stated below. to transmit data between the VLT 5000 control Data Update card and the DeviceNet option card.
  • Page 15: Fieldbus Profile

    212. Bit 02 = "0" leads to a quick stop and leads to output relay 01 or 04 being activated, when the output frequency is 0 Hz, provided Relay 123 has been MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 16 509 will be used. Bit 10, Data not valid/valid: Used for telling VLT 5000 whether the control word is to be used or ignored. Bit 10 = "0" means that the control word is ignored. Bit 10 = "1" means that the control word is used.
  • Page 17: Status Word

    Bit 03, No fault/trip: inputs as a logical "or" function. Bit 03 = "0" means that VLT 5000 Series is not in a fault condition. Bit 03 = "1" means that VLT 5000 Series has tripped and needs a reset signal in order to run.
  • Page 18 Bit 11, Does not run/runs: Bit 11 = "0" means that the motor is not running. Bit 11 = "1" means that VLT 5000 Series has a start signal of that the output frequency is greater than 0 Hz. Bit 12, VLT OK/stalling, autostart: Bit 12 = "0"...
  • Page 19: Control Word Under Vlt Standard

    215-218) in accordance with the following table: Preset ref. Parameter Bit 01 Bit 00 NB!: Parameter 508 is where to choose the way bits 1/12 are to be combined (gated) with the corresponding function on the digital inputs. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 20: Status Word Under Vlt Standard

    Bit 02 = "0" means that the control word bit 03 is "0" form of a 16-bit word. The value is transmitted (Coasting) or that VLT 5000 Series has tripped. as a whole number (0-32767). 16384 (4000 Hex) Bit 02 = "1" means that control word bit 03 is "1"...
  • Page 21: Control Word And Status Word Under Instance 20/70

    Bit 0 = "0" means that there is no active start command. Bit 0 = "1" means that a trip is reset. Bit 0 = "1" means that there is an active start command. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 22: Programming

    Quick Setup Function: For how to program the ordinary VLT parameters This parameter displays the actual Baud rate refer to the VLT 5000 Series Instruction Manual. of the devicenet option. Communication is established by setting the following parameters: 803 Time after bus error...
  • Page 23 Without function: Bit 10 is ignored, i.e. the control word and speed reference value are always valid. = factory setting. () = display text [] = value for use in communication via serial communication port MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 24 DeviceNet is not active. - With DeviceNet: Parameter processing through the DeviceNet is active = factory setting. () = display text [] = value for use in communication via serial communication port MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 25 Parameter setup 3 (SETUP 3) [ 3] Parameter setup 4 (SETUP 4) [ 4] = factory setting. () = display text [] = value for use in communication via serial communication port MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 26 EEPROM. NB!: Please note that continous writing via explicit message may damage the EEPROM. = factory setting. () = display text [] = value for use in communication via serial communication port MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 27: Warning And Alarm Messages

    TRUE [1] means fault. To each bit and each bit status there is a corresponding text string. = factory setting. () = display text [] = value for use in communication via serial communication port MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 28: Factory Settings

    Integer 16 This number refers to a conversion figure to Integer 32 Unsigned 8 be used when writing or reading by means of Unsigned 16 a VLT frequency converter. Unsigned 32 Text string MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 29 I I I I n n n n i i i i t t t t i i i i a a a a l l l l v v v v o o o o l l l l t t t t a a a a g g g g e e e e 0.0 V MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 30 M M M M o o o o t t t t o o o o r r r r p p p p h h h h a a a a s s s s e e e e m m m m o o o o n n n n i i i i t t t t o o o o r r r r Enable MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 31 F F F F r r r r e e e e e e e e z z z z e e e e r r r r e e e e f f f f e e e e r r r r e e e e n n n n c c c c e e e e / / / / o o o o u u u u t t t t p p p p u u u u t t t t f f f f u u u u n n n n c c c c t t t t i i i i o o o o n n n n No operation MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 32 M M M M a a a a i i i i n n n n s s s s v v v v o o o o l l l l t t t t a a a a g g g g e e e e a a a a t t t t m m m m a a a a i i i i n n n n s s s s f f f f a a a a u u u u l l l l t t t t Depends on unit MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 33 D D D D a a a a t t t t a a a a r r r r e e e e a a a a d d d d - - - - o o o o u u u u t t t t : : : : W W W W a a a a r r r r n n n n i i i i n n n n g g g g w w w w o o o o r r r r d d d d , , , , 2 2 2 2 MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 34 N N N N a a a a m m m m e e e e p p p p l l l l a a a a t t t t e e e e : : : : C C C C o o o o m m m m m m m m u u u u n n n n i i i i c c c c a a a a t t t t i i i i o o o o n n n n o o o o p p p p t t t t i i i i o o o o n n n n o o o o r r r r d d d d e e e e r r r r i i i i n n n n g g g g n n n n o o o o ..MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 35 R R R R e e e e l l l l a a a a y y y y 9 9 9 9 , , , , O O O O F F F F F F F F d d d d e e e e l l l l a a a a y y y y 0 sec. NB!: This VLT Parameter List is only valid when Relay Option is installed. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 36 Sync/Pos option is installed. 1) The maximum range is to 2 - 1 (-2147483648 to 2147483647) but the actual range is specified when defining a user parameter in the application program using LINKGPAR or LINKAXPAR. MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 37 M M M M o o o o d d d d i i i i f f f f i i i i e e e e d d d d p p p p a a a a r r r r a a a a m m m m e e e e t t t t e e e e r r r r s s s s ** Automatic reset to (0) S Only in stop mode (VLT must be stopped in order to change data value) MG.50.H4.02 - VLT is a registered Danfoss trademark...
  • Page 38 XREF__BC NOT LOADED ON RIP ® 5000/ 5000 FLUX/ 6000 HVAC/ 8000 AQUA Operating Instructions 175R5287 MG50H402 REV. 2003-06-26 *MG50H402*...