Motor Setup - Danfoss VLT HVAC Drive FC 131 Programming Manual

Hide thumbs Also See for VLT HVAC Drive FC 131:
Table of Contents

Advertisement

VLT® HVAC Drive FC 131
Programming Guide
Parameter
Option/range
Low Ref./Feedb.
Value
Parameter 6-25
-4999–4999
Terminal 54
High Ref./
Feedb. Value
0.00–10.00 s
Parameter 6-26
Terminal 54 Fil-
ter Time Con-
stant
Parameter 6-29
[0] Current
Terminal 54
[1] Voltage
mode
Parameter
[0] Normal
20-81 PI Nor-
[1] Inverse
mal/Inverse
Control
0–200 Hz
Parameter
20-83 PI Start
Speed [Hz]
Parameter
0.00–10.00
20-93 PI Propor-
tional Gain
0.1–999.0 s
Parameter
20-94 PI Inte-
gral Time
Parameter
[0] Off
30-22 Locked
[1] On
Rotor Detection
0.05–1.00 s
Parameter
30-23 Locked
Rotor Detection
Time [s]

3.2.2.5 Motor Setup

The motor setup wizard guides users through the needed motor parameters.
Table 8: Motor Setup Wizard Settings
Parameter
Option/range
Parameter 0-03
[0] International
Regional Set-
[1] US
tings
Parameter 0-06
[0] 200–240 V/50 Hz/IT-grid
GridType
[1] 200–240 V/50 Hz/Delta
[2] 200–240 V/50 Hz
[10] 380–440 V/50 Hz/IT-grid
[11] 380–440 V/50 Hz/Delta
[12] 380–440 V/50 Hz
24 | Danfoss A/S © 2022.05
Default
Usage
50
Enter the feedback value that corresponds to the voltage or
current set in parameter 6-21 Terminal 54 High Voltage/pa-
rameter 6-23 Terminal 54 High Current.
Enter the filter time constant.
0.01
Select if terminal 54 is used for current or voltage input.
[1] Voltage
[0] Normal
Select [0] Normal to set the process control to increase the
output speed when the process error is positive. Select [1] In-
verse to reduce the output speed.
Enter the motor speed to be attained as a start signal for
0 Hz
commencement of PI control.
0.01
Enter the process controller proportional gain. Quick control
is obtained at high amplification. However, if amplification is
too high, the process may become unstable.
Enter the process controller integral time. Obtain quick con-
999.0 s
trol through a short integral time, though if the integral time
is too short, the process becomes unstable. An excessively
long integral time disables the integral action.
[0] Off
0.10 s
Default
Usage
[0] Interna-
tional
Size selected
Select the operating mode for restart after reconnection of
the drive to mains voltage after power down.
Programming
AU370727746889en-000101 / 130R0994