7.11 Danfoss FC Control Profile

7.11.1 Control Word According to FC Profile
(8-10 Protocol = FC profile)
Master-follower
CTW
Bit
no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Illustration 7.14 Control Word According to FC Profile
Bit
Bit value=0
Bit value=1
00
Reference value
External selection lsb
01
Reference value
External selection msb
02
DC brake
Ramp
03
Coasting
No coasting
04
Quick stop
Ramp
05
Hold output
Use ramp
frequency
06
Ramp stop
Start
07
No function
Reset
08
No function
Jog
09
Ramp 1
Ramp 2
10
Data invalid
Data valid
11
Relay 01 open
Relay 01 active
12
Relay 02 open
Relay 02 active
13
Parameter set-up
Selection lsb
15
No function
Reverse
Table 7.34 Control Word According to FC Profile
Explanation of the control bits
Bits 00/01
Bits 00 and 01 are used to select between the 4 reference
values, which are pre-programmed in parameter 3-10 Preset
Reference according to Table 7.35.
Programmed
Parameter
reference
value
1
Parameter 3-10 Preset Reference [0] 0
2
Parameter 3-10 Preset Reference [1] 0
3
Parameter 3-10 Preset Reference [2] 1
4
Parameter 3-10 Preset Reference [3] 1
Table 7.35 Control Bits
NOTICE
Make a selection in parameter 8-56 Preset Reference Select
to define how bit 00/01 gates with the corresponding
function on the digital inputs.
MG18N202
Design Guide
Bit 02, DC brake
Bit 02=0 leads to DC braking and stop. Set braking current
and duration in parameter 2-01 DC Brake Current and
parameter 2-02 DC Braking Time.
Bit 02=1 leads to ramping.
Bit 03, Coasting
Bit 03=0: The frequency converter immediately releases the
Speed ref.
compressor, (the output transistors are shut off) and it
coasts to a standstill.
Bit 03=1: The frequency converter starts the compressor if
the other starting conditions are met.
Make a selection in parameter 8-50 Coasting Select to
define how bit 03 gates with the corresponding function
on a digital input.
Bit 04, Quick stop
Bit 04=0: Makes the compressor speed ramp down to stop
(set in parameter 3-81 Quick Stop Ramp Time).
Bit 05, Hold output frequency
Bit 05=0: The present output frequency (in Hz) freezes.
Change the frozen output frequency only with the digital
inputs (parameter 5-10 Terminal 18 Digital Input to
parameter 5-13 Terminal 29 Digital Input) programmed to
Speed up=21 and Slow down=22.
NOTICE
If freeze output is active, the frequency converter can
only be stopped by the following:
Bit 06, Ramp stop/start
Bit 06=0: Causes a stop and makes the compressor speed
ramp down to stop via the selected ramp down parameter.
Bit 06=1: Permits the frequency converter to start the
Bit
Bit
compressor, if the other starting conditions are met.
01
00
Make a selection in parameter 8-53 Start Select to define
how bit 06 Ramp stop/start gates with the corresponding
0
function on a digital input.
1
Bit 07, Reset
0
Bit 07=0: No reset.
1
Bit 07=1: Resets a trip. Reset is activated on the signal's
leading edge, that is, when changing from logic 0 to logic
1.
Bit 08, Jog
Bit 08=1: The output frequency is determined by
parameter 3-11 Jog Speed [Hz].
Danfoss A/S © 12/2015 All rights reserved.
Bit 03 Coasting stop
Bit 02 DC braking
Digital input (parameter 5-10 Terminal 18 Digital
Input to parameter 5-13 Terminal 29 Digital
Input) programmed to [5] DC braking, [2]
Coasting stop, or [3] Reset and coasting stop.
7
7
65