5.2.1
Changing the control method
Set the control method.
V/F control, Advanced magnetic flux vector control, and PM motor control are the control methods available for
selection.
When using an IPM motor MM-EFS or MM-THE4, simply performing the IPM parameter initialization enables the PM
motor control.
• The PM motor test operation can be performed by setting Pr.800 Control method selection.
Pr.
Name
71
Applied motor
C100
80
Motor capacity
C101
81
Number of motor poles
C102
83
Rated motor voltage
C104
84
Rated motor frequency
C105
800
Control method
G200
selection
For theFR-F820-02330(55K) or lower, and theFR-F840-01160(55K)or lower.
For theFR-F820-03160(75K) or higher and theFR-F840-01800(75K)or higher.
The initial value differs according to the voltage class. (200V class/400V class)
When the IPM motor MM-EFS or MM-THE4 is selected by Pr.71 Applied motor, the rated frequency of the MM-EFS or MM-THE4 is used.
When a PM motor other than the MM-EFS or MM-THE4 is selected by Pr.71, 75 Hz (for the motor capacity 15 kW or lower) or 100 Hz (18.5 kW
or higher) is used.
Initial
Setting range
value
0 to 6, 13 to 16, 20, 23,
24, 40, 43, 44, 50, 53, 54,
0
70, 73, 74, 210, 213, 214,
8090, 8093, 8094, 9090,
9093, 9094
0.4 to 55 kW
9999
0 to 3600 kW
9999
2, 4, 6, 8, 10, 12
9999
9999
200/400V
0 to 1000 V
10 to 400Hz
9999
9999
9
20
20
Control method
Description
By selecting a standard motor or constant-torque
motor, the thermal characteristic and motor constant
of each motor are set.
Set the applied motor capacity.
V/F control
Set the number of motor poles.
V/F control
Set the rated motor voltage (V).
Set the rated motor frequency (Hz).
The setting value of Pr.3 Base frequency is used.
PM motor test operation (Motor is not driven even if it
is connected.)
Normal operation (Motor can be driven.)
PARAMETERS
5
143