5.4.12

Parameter write selection

Whether to enable the writing to various parameters or not can be selected. Use this function to prevent parameter
values from being rewritten by misoperation.
Pr.
Name
77
Parameter write selection
E400
• Pr.77 can be set at any time regardless of the operation mode or operation status. (Setting through communication is unavailable.)
Writing parameters only during stop (Pr.77 = "0" initial value)
• Parameters can be written only during a stop in the PU operation mode.
• The following parameters can always be written regardless of the operation mode or operation status.
Pr.
(Multi-speed setting high-speed, middle-speed,
4 to 6
low-speed)
22
Stall prevention operation level
24 to 27
(Multi-speed setting speed 4 to speed 7)
52
Operation panel main monitor selection
54
FM/CA terminal function selection
55
Frequency monitoring reference
56
Current monitoring reference
72
PWM frequency selection

Reset selection/disconnected PU detection/PU
75
stop selection
77
Parameter write selection
79
Operation mode selection

129
PID proportional band
130
PID integral time
133
PID action set point
134
PID differential time
158
AM terminal function selection
160
User group read selection
232 to 239
(Multi-speed setting speed 8 to speed 15)
240
Soft-PWM operation selection

241
Analog input display unit switchover
268
Monitor decimal digits selection
290
Monitor negative output selection
295
Frequency change increment amount setting
296, 297
(Password setting)
306
Analog output signal selection
310
Analog meter voltage output selection
340
Communication startup mode selection

345, 346
(DeviceNet communication)
416, 417
(PLC function)
434, 435
(CC-Link communication)
496, 497
(Remote output)
498
PLC function flash memory clear

Writing during operation is enabled in PU operation mode, but disabled in External operation mode.

Writing during operation is disabled. To change the parameter setting value, stop the operation.
Initial value
0
Name
(E) Environment setting parameters
Setting range
0
Writing is enabled only during stop.
1
Parameter writing is disabled.
Parameter writing is enabled in any operation
2
mode regardless of the operation status.
Pr.
NET mode operation command source
550

selection
551
PU mode operation command source selection

555 to 557
(Current average value monitor)
656 to 659
(Analog remote output)
663
Control circuit temperature signal output level
755 to 758
(Second PID control)
759
PID unit selection
774 to 776
(PU/DU monitor selection)
866
Torque monitoring reference
888, 889
(Free parameter)
891 to 899
(Energy saving monitor)
C0 (900)
FM/CA terminal calibration
C1 (901)
AM terminal calibration
C8 (930)
Current output bias signal
C9 (930)
Current output bias current
C10 (931)
Current output gain signal
C11 (931)
Current output gain current
990
PU buzzer control
991
PU contrast adjustment
Operation panel setting dial push monitor
992
selection
997
Fault initiation
998
PM parameter initialization

999
Automatic parameter setting

1006
Clock (year)
1007
Clock (month, day)
1008
Clock (hour, minute)
1019
Analog meter voltage negative output selection
1048
Display-off waiting time
1142
Second PID unit selection
1150 to 1199
(PLC function user parameters)
1211 to 1219 (PID gain tunig)
1460 to 1466 (PID multistage set points 1 to 7)
1480 to 1485 (Load characteristics fault detection)
Description
Name
169
PARAMETERS
5
GROUP