Mitsubishi Electric FR-F800 Instruction Manual page 394

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

Classification
signal
X14
Input signal
X64
X72
FUP
FDN
RL
Output signal
PID
SLEEP
Y48
NOTE
• Even if the X14 signal is ON, PID control is stopped and multi-speed or JOG operation is performed when the RH, RM, RL, or
REX signal (multi-speed operation) or JOG signal (JOG operation) is input.
• PID control is invalid under the following settings.
Pr.79 Operation mode selection = "6" (Switchover mode)
• Note that input to the terminal 1 is added to the terminals 2 and 4 inputs. For example when Pr.128 = "20 or 21", the terminal
1 input is considered as a set point and added to the set point of the terminal 2.
• To use terminal 4 and 1 inputs in PID control, set "0" (initial value) to Pr.858 Terminal 4 function assignment and Pr.868
Terminal 1 function assignment. When a value other than "0", PID control is invalid.
• Changing the terminal assignment using Pr.178 to Pr.189 or Pr.190 to Pr.196 may affect other functions. Set parameters
after confirming the function of each terminal.
• When PID control is selected, the minimum frequency becomes the frequency of Pr.902 and the maximum frequency
becomes the frequency of Pr.903.
(The Pr.1 Maximum frequency and Pr.2 Minimum frequency settings also are valid.)
• During PID operation, the remote operation function is invalid.
• When control is switched to PID control during normal operation, the frequency during that operation is not carried over, and
the value resulting from PID calculation referenced to 0 Hz becomes the command frequency.
Parameters referred to
Pr.59 Remote function selection
Pr.73 Analog input selection
page 306
Pr.79 Operation mode selection
Pr.178 to Pr.189 (input terminal function selection)
Pr.190 to Pr.196 (output terminal function selection)
Pr.290 Monitor negative output selection
C2 (Pr.902) to C7 (Pr.905) Frequency setting voltage (current) bias/gain
First PID function parameters
Name
PID control valid terminal
PID forward/reverse action switchover
PID integral value reset
PID upper limit
PID lower limit
PID forward/reverse rotation output
During PID control activated
PID output interruption
PID deviation limit
PID set point
Frequency
command
PID action
Normal operation
Operation when control is switched to PID control during normal operation
page 194
page 200
page 329
page 288
page 273
Second PID function parameters
signal
X80
Second PID control valid terminal
Second PID forward/reverse action
X79
switchover
X73
Second PID P control switchover
FUP2
Second PID upper limit
FDN2
Second PID lower limit
RL2
Second PID forward/reverse rotation output
PID2
Second During PID control activated
SLEEP2
During second PID output shutoff
Y205
Second PID deviation limit
Frequency command
during normal operation
ON
PID operation
Normal operation
page 314
(A) Application parameters
Name
PARAMETERS
5
GROUP
A
393