Pid Operation Function; Bypass Function; Backlash Measures Function; Current Detection Function - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

Parameter List
Parameter list (by parameter number)
Pr.
Pr.
group
PID control automatic switchover
127
A612
frequency
128
A610
PID action selection
129
A613
PID proportional band
130
A614
PID integral time
131
A601
PID upper limit
132
A602
PID lower limit
133
A611
PID action set point
134
A615
PID differential time
Electronic bypass sequence
135
A000
selection
136
A001
MC switchover interlock time
137
A002
Start waiting time
138
A003
Bypass selection at a fault
Automatic switchover frequency
139
A004
from inverter to bypass operation
Backlash acceleration stopping
140
F200
frequency
Backlash acceleration stopping
141
F201
time
Backlash deceleration stopping
142
F202
frequency
Backlash deceleration stopping
143
F203
time
144
M002
Speed setting switchover
145
E103
PU display language selection
Acceleration/deceleration time
147
F022
switching frequency
148
H620
Stall prevention level at 0 V input
149
H621
Stall prevention level at 10 V input
150
M460
Output current detection level
Output current detection signal
151
M461
delay time
152
M462
Zero current detection level
153
M463
Zero current detection time
Voltage reduction selection during
154
H631
stall prevention operation
RT signal function validity
155
T730
condition selection
156
H501
Stall prevention operation selection 0 to 31, 100, 101
157
M430
OL signal output timer
158
M301
AM terminal function selection
Automatic switchover frequency
159
A005
range from bypass to inverter
operation
160
E440
User group read selection
Frequency setting/key lock
161
E200
operation selection
116
PARAMETERS
Name
Setting range
0 to 590 Hz, 9999
0, 10, 11, 20, 21,
50, 51, 60, 61, 70, 71,
80, 81, 90, 91, 100,
101, 1000, 1001,
1010, 1011, 2000,
2001, 2010, 2011
0.1 to 1000%, 9999
0.1 to 3600 s, 9999
0 to 100%, 9999
0 to 100%, 9999
0 to 100%, 9999
0.01 to 10 s, 9999
0, 1
0 to 100 s
0 to 100 s
0, 1
0 to 60 Hz, 9999
0 to 590 Hz
0 to 360 s
0 to 590 Hz
0 to 360 s
0, 2, 4, 6, 8, 10, 12,
102, 104, 106, 108,
110, 112
0 to 7
0 to 590 Hz, 9999
0 to 400%
0 to 400%
0 to 400%
0 to 10 s
0 to 400%
0 to 10 s
0, 1, 10, 11
0, 10
0 to 25 s, 9999
1 to 3, 5 to 14, 17, 18,
21, 24, 34, 50, 52 to
54, 61, 62, 67, 70,
86 to 96, 98
0 to 10 Hz, 9999
0, 1, 9999
Simple
Simple
Simple
0, 1, 10, 11
Initial value
Minimum
setting
FM
CA
increments
0.01 Hz
9999
1
0
0.1%
100%
0.1 s
1 s
0.1%
9999
0.1%
9999
0.01%
9999
0.01 s
9999
1
0
0.1 s
1 s
0.1 s
0.5 s
1
0
0.01 Hz
9999
0.01 Hz
1 Hz
0.1 s
0.5 s
0.01 Hz
1 Hz
0.1 s
0.5 s
1
4
1
1
0.01 Hz
9999
0.1%
120%
110%
0.1%
150%
120%
0.1%
120%
110%
0.1 s
0 s
0.1%
5%
0.01 s
0.5 s
1
1
1
0
1
0
0.1 s
0 s
1
1
0.01 Hz
9999
1
9999
0
1
0
Refer
to
page
378
378
378
378
378
378
378
378
363
363
363
363
363
191
191
191
191
261
164
187
248
248
296
296
296
296
248
333
248
248
273
363
177
166

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents