Mitsubishi Electric FR-F800 Instruction Manual page 343

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

(C) Motor constant parameters
Pr.
Name
298
Frequency search
A711
gain
450
Second applied
C200
motor
453
Second motor
C201
capacity
454
Number of second
C202
motor poles
51
Second electronic
C203
thermal O/L relay
456
Rated second motor
C204
voltage
457
Rated second motor
C205
frequency
744
Second motor inertia
C207
(integer)
745
Second motor inertia
C208
(exponent)
463
Second motor auto
C210
tuning setting/status
458
Second motor
C220
constant (R1)
459
Second motor
C221
constant (R2)
Second motor
460
constant (L1) / d-axis
C222
inductance (Ld)
Second motor
461
constant (L2) / q-axis
C223
inductance (Lq)
462
Second motor
C224
constant (X)
455
Second motor
C225
excitation current
Second motor torque
860
current/Rated PM
C226
motor current
560
Second frequency
A712
search gain

For the FR-F820-02330(55K) or lower and FR-F840-01160(55K)or lower.

For the FR-F820-03160(75K) or higher and FR-F840-01800(75K)or higher.

Differs according to the voltage class. (200 V/400 V)

The setting range and unit change according to the Pr.71 (Pr.450) setting.
342
PARAMETERS
Initial
Setting range
value
0 to 32767
9999
9999
0, 1, 3 to 6, 13 to 16, 20, 23, 24,
40, 43, 44, 50, 53, 54, 70, 73,
74, 210, 213, 214, 8090, 8093,
9999
8094, 9090, 9093, 9094
9999
0.4 to 55 kW

9999
0 to 3600 kW

9999
2, 4, 6, 8, 10, 12
9999
9999
0 to 500 A

9999
0 to 3600 A

9999
200/400 V
0 to 1000 V

10 to 400 Hz
9999
9999
9999
10 to 999, 9999
9999
10 to 7, 9999
0
1
0
11
101
0 to 50 Ω, 9999
9999
0 to 400 mΩ, 9999
0 to 50 Ω, 9999
9999
0 to 400 mΩ, 9999
0 to 6000 mH, 9999
9999
0 to 400 mH, 9999
0 to 6000 mH, 9999
9999
0 to 400 mH, 9999
9999
0 to 100%, 9999
0 to 500 A, 9999
9999
0 to 3600 A, 9999
0 to 500 A, 9999
9999
0 to 3600 A, 9999
0 to 32767
9999
9999
The offline auto tuning automatically sets the
gain required for the frequency search.
Uses the constant value of Mitsubishi motor (SF-
PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA and so
on).
Set this parameter when using the second motor.
(the same specifications as Pr.71).
The function is disabled.
Set the capacity of the second motor.
V/F control
Set the number of poles of the second motor.
V/F control
This function is enabled when the RT signal is
ON.
Set the rated motor current.
Second electronic thermal O/L relay disabled
Set the rated voltage (V) of the second motor.
Set the rated frequency (Hz) of the second motor.
Use the Pr.84 Rated motor frequency setting.
Set the inertia of the second motor.
9999: Uses the constant value of Mitsubishi
motor (SF-PR, SF-JR, SF-HR, SF-JRCA, SF-
HRCA and so on).
No auto tuning for the second motor.
Performs offline auto tuning without rotating the
second motor
Performs offline auto tuning without rotating the
motor (V/F control, IPM motor MM-EFS/MM-
THE4)
(Refer to
page
Performs offline auto tuning by rotating the
second motor
 
 
 
 
 
 
Tuning data of the second motor
(The value measured by offline auto tuning is
 
automatically set.)
9999: Uses the constant value of Mitsubishi
 
motor (SF-PR, SF-JR, SF-HR, SF-JRCA, SF-
HRCA and so on).

 
 
 
 
The offline auto tuning automatically sets the
gain required for the frequency search of the
second motor.
Uses the constant value of Mitsubishi motor (SF-
PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA and so
on).
Description
351)