Pr.
Pr.
group
1460
A683
PID multistage set point 1
1461
A684
PID multistage set point 2
1462
A685
PID multistage set point 3
1463
A686
PID multistage set point 4
1464
A687
PID multistage set point 5
1465
A688
PID multistage set point 6
1466
A689
PID multistage set point 7
1469
A420
Number of cleaning times monitor
1470
A421
Number of cleaning times setting
1471
A422
Cleaning trigger selection
1472
A423
Cleaning reverse rotation frequency 0 to 590 Hz
Cleaning reverse rotation operation
1473
A424
time
Cleaning forward rotation
1474
A425
frequency
Cleaning forward rotation operation
1475
A426
time
1476
A427
Cleaning stop time
1477
A428
Cleaning acceleration time
1478
A429
Cleaning deceleration time
1479
A430
Cleaning time trigger
Load characteristics measurement
1480
H520
mode
Load characteristics load reference
1481
H521
1
Load characteristics load reference
1482
H522
2
Load characteristics load reference
1483
H523
3
Load characteristics load reference
1484
H524
4
Load characteristics load reference
1485
H525
5
Load characteristics maximum
1486
H526
frequency
Load characteristics minimum
1487
H527
frequency
1488
H530
Upper limit warning detection width 0 to 400%, 9999
1489
H531
Lower limit warning detection width 0 to 400%, 9999
1490
H532
Upper limit fault detection width
1491
H533
Lower limit fault detection width
Load status detection signal delay
1492
H534
time / load reference measurement
waiting time
Pr.CLR
Parameter clear
ALL.CL
All parameter clear
Err.CL
Fault history clear
Name
Setting range
0 to 100%, 9999
0 to 100%, 9999
0 to 100%, 9999
0 to 100%, 9999
0 to 100%, 9999
0 to 100%, 9999
0 to 100%, 9999
0 to 255
0 to 255
0 to 15
0 to 3600 s
0 to 590 Hz, 9999
0 to 3600 s, 9999
0 to 3600 s
0 to 3600 s, 9999
0 to 3600 s, 9999
0 to 6000 h
0, 1 (2 to 5, 81 to 85)
0 to 400%, 8888,
9999
0 to 400%, 8888,
9999
0 to 400%, 8888,
9999
0 to 400%, 8888,
9999
0 to 400%, 8888,
9999
0 to 590 Hz
0 to 590 Hz
0 to 400%, 9999
0 to 400%, 9999
0 to 60 s
(0), 1
(0), 1
(0), 1
Parameter list (by parameter number)
Initial value
Minimum
setting
FM
CA
increments
0.01%
9999
0.01%
9999
0.01%
9999
0.01%
9999
0.01%
9999
0.01%
9999
0.01%
9999
1
0
1
0
1
0
0.01 Hz
30 Hz
0.1 s
5 s
0.01 Hz
9999
0.1 s
9999
0.1 s
5 s
0.1 s
9999
0.1 s
9999
0.1 h
0 h
1
0
0.1%
9999
0.1%
9999
0.1%
9999
0.1%
9999
0.1%
9999
0.01 Hz
60 Hz 50 Hz
0.01 Hz
6 Hz
0.1%
20%
0.1%
20%
0.1%
9999
0.1%
9999
0.1 s
1 s
1
0
1
0
1
0
PARAMETERS
Parameter List
Refer
to
page
Pr.
378
List
378
378
378
378
378
378
375
375
375
375
375
375
375
375
375
375
375
255
255
255
255
255
255
255
255
255
255
255
255
5
255
520
520
531
131

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents