(E) Environment setting parameters
5.4.2
Reset selection/disconnected PU detection/PU
stop selection
The reset input acceptance, disconnected PU (operation panel/paprameter unit) connector detection function and PU
stop function (PU stop) can be selected.
Pr.
Name
Reset selection/disconnected
75
PU detection/PU stop selection
E100
Reset selection
E101
Disconnected PU detection
E102
PU stop selection
E107
Reset limit
The parameters above will not return to their initial values even if parameter (all) clear is executed.

The setting range for the FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.

The setting range for the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
Pr.75
Setting

0, 100
Reset input always enabled
Reset input enabled only when
1, 101
protective function activated
2, 102
Reset input always enabled
Reset input enabled only when
3, 103
protective function activated
14 (Initial
Reset input always enabled
value), 114
Reset input enabled only when
15, 115
protective function activated
16, 116
Reset input always enabled
Reset input enabled only when
17, 117
protective function activated

Setting Pr.75 = any of "100 to 103 and 114 to 117" will enable the reset limit function. The setting is available for the FR-F820-03160(75K) or
higher and FR-F840-01800(75K) or higher.
Reset selection (P.E100)
• When P.E100="1" or Pr.75="1, 3, 15, 17, 100, 103, 115, or 117" is set, reset (reset command via RES signal or
communication) input is enabled only when the protective function is activated.
NOTE
• When the reset signal (RES) is input during operation, the motor coasts since the inverter being reset shuts off the output.
Also, the cumulative values of electronic thermal O/L relay and regenerative brake duty are cleared.
• The input of the PU reset key is only enabled when the protective function is activated, regardless of the P.E100 and Pr.75
settings.
162
PARAMETERS
Initial
value
14
0
0
1
0
Reset selection
Setting range
0 to 3, 14 to 17

0 to 3, 14 to 17,
100 to 103, 114 to 117

0
1
0
1
0
1
0
1

Disconnected PU detection
Operation continues even when PU
is disconnected.
Inverter output shut off when PU
disconnected.
Operation continues even when PU
is disconnected.
Inverter output shut off when PU
disconnected.
Description
For the initial setting, reset is always
enabled, without disconnected PU detection,
and with the PU stop function.
Reset input is always enabled.
Reset input is enabled only when the
protective function is activated.
Operation continues even when the PU is
disconnected.
The inverter output is shut off when the PU is
disconnected.
Decelerates to a stop when the STOP key is
pressed in PU operation mode only.
Decelerates to a stop when the STOP key
for PU is pressed in any of the PU, external
and communication operation modes.
Reset limit disabled
Reset limit enabled
PU stop selection
Decelerates to a stop when
input in PU operation mode only.
Decelerates to a stop when
input in any of the PU, external and
communication operation modes.
is
is