(M) Monitor display and monitor output signal

When using the item as the main monitor data on the LCD operation panel (FR-LU08) or the parameter unit (FR-PU07), use Pr.774 to Pr.776 or
the monitor function of the FR-LU08 or the FR-PU07 for setting.

The cumulative energization time and actual operation time are accumulated from 0 to 65535 hours, then cleared, and accumulated again from
0.

The actual operation time does not increase if the cumulative running time before power OFF is less than an hour.

When using the parameter unit (FR-PU07), "kW" is displayed.

Differs according to capacities. (FR-F820-02330(55K) or lower, FR-F840-01160(55K) or lower /FR-F820-03160(75K) or higher, FR-F840-
01800(75K) or higher)

Since the voltage and current display on the operation panel (FR-DU08) is shown in four digits, a monitor value of more than "9999" is displayed
as "----".

The setting is available only for standard models.

When the output current is less than the specified current level (5% of the rated inverter current), the output current is monitored as 0 A.
Therefore, the monitored value of an output current and output power may be displayed as "0" when using a much smaller-capacity motor
compared to the inverter or in other instances that cause the output current to fall below the specified value.

Available when the plug-in option is connected.
 Input terminal monitor details ("1" denotes terminal ON, "0" denotes terminal OFF, and "―" denotes undetermined value.)
b15
 Output terminal monitor details ("1" denotes terminal ON, "0" denotes terminal OFF, and "―" denotes undetermined value.)
b15
 Option input terminal monitor 1 details (FR-A8AX input terminal status, "1" denotes terminal ON and "0" denotes terminal OFF.) ―― All are OFF
when the option is not connected.
b15
X15
X14
X13
X12
 Option input terminal monitor 2 details (FR-A8AX input terminal status. "1" denotes terminal ON, "0" denotes terminal OFF, "―" denotes
undetermined value.) ―― All are OFF when the option is not connected.
b15
 Option output terminal monitor details (FR-A8AY/A8AR output terminal status. "1" denotes terminal ON, "0" denotes terminal OFF, and "―" denotes
undetermined value.)―― All are OFF when the option is not connected.
b15
 The increment is 1 when Pr.37 = "1 to 9998" or when Pr.144 = "2 to 12" or "102 to 112". (Refer to
 The monitored values are retained even if an inverter fault occurs. Resetting will clear the retained values.
 Parameter setting is not available for setting the item as the main monitor data on the LCD operation panel (FR-LU08) or the parameter unit (FR-
PU07). Use the monitor function of the FR-LU08 or the FR-PU07 for setting.
268
PARAMETERS
STP
CS
RES
(STOP)
X11
X10
X9
RA3
MRS
JOG
RH
RM
SO
ABC2
ABC1
X8
X7
X6
X5
RA2
RA1
Y6
Y5
RL
RT
AU
STR
FU
OL
IPF
SU
X4
X3
X2
X1
Y4
Y3
Y2
Y1
page
261.)
b0
STF
b0
RUN
b0
X0
b0
DY
b0
Y0