2.8.5
Connection of the power regeneration common
converter (FR-CV)
When connecting the power regeneration common converter (FR-CV), connect the inverter terminals (P/+, N/-) and the power
regeneration common converter (FR-CV) terminals as shown below so that their symbols match with each other.
The FR-CV is applicable to FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.
After making sure that the wiring is correct, set "2" in Pr.30 Regenerative function selection. (Refer to
MCCB
Three-phase
AC power
supply
Remove jumpers between terminals R/L1 and R1/L11 as well as between S/L2 and S1/L21, and connect the power supply for the
control circuit to terminals R1/L11 and S1/L21. Do not connect anything to power input terminals (R/L1, S/L2, T/L3). Incorrect
connection will damage the inverter. (E.OPT (option fault) will occur. (Refer to
Do not insert an MCCB between terminals P/+ and N/- (between terminals P/L+ and P/+ or between N/L- and N/-). Connecting the
opposite polarity of terminals N/- and P/+ will damage the inverter.
Use Pr.178 to Pr.189 (input terminal function selection) to assign the terminals used for the X10 signal. (Refer to
Be sure to connect the power supply and terminals R/L11, S/L21, and T/MC1. Operating the inverter without connecting them will
damage the power regeneration common converter.
Always connect terminal RDYB of the FR-CV to the inverter terminal where the X10 signal or the MRS signal is assigned to. Always
connect terminal SE of the FR-CV to the inverter terminal SD. Not connecting these terminals may damage the FR-CV.
NOTE
• The voltage phases of terminals R/L11, S/L21, and T/MC1 and the voltage phases of terminals R2/L1, S2/L2, and T2/L3 must
be matched.
• Use the sink logic (factory setting) when the FR-CV is connected. It cannot be connected when the source logic is selected.
• Do not connect a DC reactor (FR-HEL) to the inverter when FR-CV is connected.
Dedicated stand-alone
reactor (FR-CVL)
MC1
R/L11
R2/L12
S/L21
S2/L22
T/L31
T2/L32
Connection of stand-alone option units
R/L1
S/L2
T/L3
R1/L11
S1/L21
FR-CV type
Power regeneration
common converter
R2/L1
S2/L2
P/L+
P/+
T2/L3
N/-
N/L-
P24
PC
R/L11
SD
SD
S/L21
∗4
RDYA
∗5
T/MC1
RDYB
X10
RSO
RES
SE
page
546.)
INSTALLATION AND WIRING
page
508.)
U
∗1
V
M
W
Inverter
∗2
∗3
page
329.)
67
2