Supported Bacnet Object; Analog Input; Analog Output; Analog Value - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

(N) Operation via communication and its settings
Supported BACnet object
 ANALOG INPUT
Object
Object name
identifier
0
Terminal 1
1
Terminal 2
2
Terminal 4

R: Read only, W: Read/Write (Commandable values not supported), C: Read/Write (Commandable values supported)
 ANALOG OUTPUT
Object
Object name
identifier
0
Terminal FM (CA)
1
Terminal AM

R: Read only, W: Read/Write (Commandable values not supported), C: Read/Write (Commandable values supported)
Values written to the objects that support the commandable values are stored in the Priority Array, even when "Write Access Denied" is returned
due to inconsistency of the writing requirements such as the operating mode, on condition that the values are written within the setting range.

Available regardless of the operation mode, operation command source, and speed command source.
 ANALOG VALUE
Object
Object name
identifier
1
Output frequency
2
Output current
3
Output voltage
6
Running speed
Converter output
8
voltage
14
Output power
17
Load meter
Cumulative
20
energization time
23
Actual operation time
484
PARAMETERS
Present value
access type

Represents actual input voltage of terminal 1.
(The range varies depending on the Pr.73 and Pr.267
R
settings.
-10 to +10 V (-100% to +100%),
-5 to +5 V (-100% to +100%))
Represents actual input voltage (or input current) of terminal
2.
(The range varies depending on the Pr.73 and Pr.267
R
settings.
0 to 10 V (0% to 100%),
0 to 5 V (0% to 100%),
0 to 20 mA (0% to 100%))
Represents actual input voltage (or input current) of terminal
4.
(The range varies depending on the Pr.73 and Pr.267
R
settings.
2 to 10 V (0% to 100%),
1 to 5 V (0% to 100%),
4 to 20 mA (0% to 100%))
Present value
access type

Controls actual output current level of terminal FM/CA.
Control is available when Pr.54 FM/CA terminal function
C
selection="85"
(Setting range: 0 to 200%)
Controls actual output voltage level of terminal AM.
Control is available when Pr.158 AM terminal function
C
selection="86"
(Setting range: -200 to 200%)
Present value
access type

R
Represents the output frequency monitor.
R
Represents the output current monitor.
R
Represents the output voltage monitor.
R
Represents the running speed monitor.
R
Represents the converter output voltage monitor.
R
Represents the output power monitor.
R
Represents the load meter monitor.
R
Represents the cumulative energization time monitor.
R
Represents the actual operation time monitor.
Description
Description
.

.

Description
Unit
percent
(98)
percent
(98)
percent
(98)
Unit
percent
(98)
percent
(98)
Unit
hertz
(27)
amperes
(3)
volts
(5)
revolution-
per-minute
(104)
volts
(5)
kilowatts
(48)
percent
(98)
hours
(71)
hours
(71)