Changing The Frequency (60 Hz, Initial Value) At The Maximum Current Input (At 20 Ma, Initial Value) - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

Basic operation procedure (External operation)
4.6.6
Changing the frequency (60 Hz, initial value) at
the maximum current input (at 20 mA, initial
value)
Change the maximum frequency.
Changing example
With a 4 to 20 mA input frequency setting potentiometer, change the frequency at 20 mA from 60 Hz
(initial value) to 50 Hz.
Adjust the setting so that the inverter outputs 50 Hz when 20 mA is input. Set "50 Hz" in Pr.126.
Parameter selection
Turn
until
1.
Press
to show the present set value. (60.00 Hz)
Changing the maximum frequency
Turn
to change the set value to "
2.
Press
to enter the setting."
Checking the mode/monitor
3.
Press
three times to change to the monitor / frequency monitor.
Start
Turn ON the start switch (STF or STR), then turn the potentiometer (frequency setting potentiometer) clockwise slowly to full.
4.
(Refer to steps 3 and 4 in 4.6.5.)
Operate at 50 Hz.
NOTE
• To set the frequency at 4 mA, use the calibration parameter C5.
• Other adjustment methods for the frequency setting current gain are the following: adjustment by applying a current through
terminals 4 and 5, and adjustment using a specified point without applying a current through terminals 4 and 5.
Parameters referred to
Pr.126 Terminal 4 frequency setting gain frequency
C5(Pr.904) Terminal 4 frequency setting bias frequency
C7(Pr.905) Terminal 4 frequency setting gain
108
BASIC OPERATION
(Pr.126) appears.
". (50.00 Hz)
" and "
60Hz
(50Hz)
Output frequency
(Hz)
Bias
C5
(Pr.904)
0
20
0
4
Frequency setting signal
0
1
0
2
C6(Pr.904)
page 314
page 314
page 314
Operation
" flicker alternately.
Initial value
Gain
100%
20mA
5V
10V
C7(Pr.905)
Pr.126