(A) Application parameters
5.11.6

PID gain tuning

Changing the PID control manipulated amount and measuring the PID control response enable automatic setting of the
constant optimal for PID control.
For tuning, use the step response method or the limit cycle method.
Pr.
Name
1211
PID gain tuning timeout
A690
time
1212
Step manipulated
A691
amount
1213
Step responding
A692
sampling cycle
1214
Timeout time after the
A693
maximum slope
1215
Limit cycle output upper
A694
limit
1216
Limit cycle output lower
A695
limit
1217
Limit cycle hysteresis
A696
1218
PID gain tuning setting
A697
1219
PID gain tuning start/
A698
status
Step response method
• In the step response method, the manipulated amount is changed step by step for the real system. From the change in the
measured values, the maximum slope (R) and the equivalent waste time (L) are calculated to determine each constant.
Manipulated
amount[%]
Measured value[%]
Equivalent
waste time L (s)
PID gain tuning start
• The step manipulated amount (Pr.1212 - 1000) is added to the present manipulated amount.
• The measured value is taken for every sampling cycle of step response (Pr.1213). From the variation between the
measured values (Y) and the time (t), the maximum slope (R) is calculated.
394
PARAMETERS
Initial
Setting range
value
100 s
1 to 9999 s
1000%
900 to 1100%
1 s
0.01 to 600 s
10 s
1 to 9999 s
1100%
900 to 1100%
1000%
900 to 1100%
1%
0.1 to 10%
0, 100 to 102, 111, 112,
0
121, 122, 200 to 202,
211, 212, 221, 222
0
1
0
2
8
9, 90 to 96
Maximum
Maximum
Maximum
slope R
slope R
slope R
(R=Y/T)
(R=Y/T)
(R=Y/T)
STF
PID
PGT
Description
Set the time after the PID gain tuning starts until a
timeout error occurs.
Set the step manipulated amount when using the step
response method to perform the PID gain tuning.
Set the cycle for sampling of measurement values when
using the step response method to perform the PID gain
tuning.
Set the time after the measurement of the maximum
slope until the completion of the tuning when using the
step response method to perform the PID gain tuning.
Set the upper limit value of the two-position output when
using the limit cycle method to perform the PID gain
tuning.
Set the lower limit value of the two-position output when
using the limit cycle method to perform the PID gain
tuning.
Set the hysteresis of the set point when using the limit
cycle method to perform the PID gain tuning.
Select the target loop, method, and control adjustment
method for the PID gain tuning.
PID gain tuning function disabled
PID gain tuning start
During PID gain tuning (read only)
PID gain tuning forced end
Tuning error (read only)
Step manipulated amount
(Pr.1212-1000)
PID gain tuning end
Measured value
variation range Y
Equivalent time constant T (s)
Timeout time after the maximum slope (s)
(Pr.1214)
Time
Time