4.2

Changing the control method and mode

Set the control method and the control mode.
V/F control, Advanced magnetic flux vector control, Real sensorless vector control, Vector control, and PM sensorless vector
control are available.
The available control modes are speed control, torque control, and position control modes.
• Select a control method and a control mode by setting Pr.800 (Pr.451) Control method selection.
• The control mode can be switched using a mode switching signal (MC).
Pr.
71
Applied motor
C100
80
Motor capacity
C101
81
Number of motor poles
C102
83
Rated motor voltage
C104
84
Rated motor frequency
C105
800
Control method selection
G200
451
Second motor control
G300
method selection
*1
The setting range for the 575 V class is "0, 3, 5, 6, 10, 13, 15, 16, 30, 33, 8090, 8093, 9090, and 9093".
*2
The initial value differs according to the inverter's voltage class (200/400/575 V).
*3
The inverter internal data is used under PM sensorless vector control.
 Setting the motor capacity and the number of motor poles (Pr.80, Pr.81)
• Motor specifications (the motor capacity and the number of motor poles) must be set to select Advanced magnetic flux
vector control, Real sensorless vector control, Vector control, or PM sensorless vector control.
• Set the motor capacity (kW) in Pr.80 Motor capacity and set the number of motor poles in Pr.81 Number of motor poles.
 Selection of the control method and the control mode
• Select a control method (and a control mode) from V/F control, Advanced magnetic flux vector control (speed control), Real
sensorless vector control (speed control, torque control), Vector control (speed control, torque control, position control),
and PM sensorless vector control (speed control).
104
4. Control Method
4.2 Changing the control method and mode
Name
Initial value
0
9999
9999
200/400/575
*2
V
9999
40
9999
Setting range
0, 3, 5, 6, 10, 13, 15,
16, 20, 23, 30, 33, 40,
By selecting a standard motor or constant-torque motor,
43, 50, 53, 70, 73,
the thermal characteristic and motor constant of each
1800, 1803, 8090,
motor are set.
*1
8093, 9090, 9093
0.1 to 30 kW
Set the applied motor capacity.
9999
No motor capacity setting
2, 4, 6, 8, 10, 12
Set the number of motor poles.
9999
No number of motor poles setting
0 to 1000 V
Set the rated motor voltage (V).
10 to 400 Hz
Set the rated motor frequency (Hz).
9999
The setting value of Pr.3 Base frequency is used.
0 to 5
Vector control
9
Vector control test operation
Real sensorless vector control / PM sensorless vector
10
control
11, 12
Real sensorless vector control
19
PM sensorless vector control test operation
20
Advanced magnetic flux vector control
40
V/F control
Real sensorless vector control / PM sensorless vector
10
control
11, 12
Real sensorless vector control
20
Advanced magnetic flux vector control
40
V/F control
9999
Control selected in Pr.800
Description
*3