(c) Adjust only frequency without adjustment of gain voltage (current)
(When changing the gain frequency from 60 Hz to 50 Hz)
Parameter selection
Turn
to choose
1.
Press
to show the present set value. (150.00%)
Torque setting change
Turn
to change the set value to "
2.
Press
to enter the setting. "
Checking the mode/monitor
3.
Press
three times to change to the monitor / frequency monitor.
Start
4.
Turn ON the start switch (STF or STR) to apply a voltage across terminals 1 and 5 (4 and 5),
Operation is performed with 130% torque.
NOTE
• If the frequency meter (display meter) connected across the terminals FM and SD (CA and 5) does not indicate exactly 60
Hz, set the calibration parameter C0 FM/CA terminal calibration. (Refer to
• If the gain and bias of voltage (current) setting voltage are too close, an error (
• Changing C4 (Pr.903) or C7 (Pr.905) (gain adjustment) will not change Pr.20.
Input to the terminal 1 (frequency setting auxiliary input) is added to the frequency setting signal.
• For operation outline of the parameter unit (FR-PU07), refer to the Instruction Manual of the FR-PU07.
• To set the value to 120 Hz or higher, the Pr.18 High speed maximum frequency needs to be 120 Hz or higher. (Refer to
page
245.)
• Make the bias frequency setting using the calibration parameter C2 (Pr.902) and C5 (Pr.904). (Refer to
Caution
 Be cautious when setting any value other than "0" as the bias frequency at 0 V (0 mA). Even if a
speed command is not given, simply turning ON the start signal will start the motor at the preset
frequency.
Parameters referred to
???????
Pr.1 Maximum frequency, Pr.18 High speed maximum frequency
Pr.20 Acceleration/deceleration reference frequency
Pr.73 Analog input selection, Pr.267 Terminal 4 input selection
Pr.79 Operation mode selection
Pr.858 Terminal 4 function assignment, Pr.868 Terminal 1 function assignment
(Pr.125) for the terminal 2, and
". (130.00%)
" and "
page 245
page 187
page 306
page 200
(T) Multi-Function Input Terminal Parameters
Operation
(Pr.126) for the terminal 4.
(
)" flicker alternately.
page
page 310
279.)
) may be displayed at setting.
page
316.)
PARAMETERS
5
GROUP
T