Selection Of Deviation Value, Measured Value And Set Point Input Method, And Pid Action Method (Pr.128, Pr.609, Pr.610) - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

Connection diagram
Sink logic
Pr.128=20
Pr.183=14
Pr.191=47
Pr.192=16
Pr.193=14
Pr.194=15

Prepare a power supply matched to the power supply specification of the detector.

The output signal terminal to be used differs according to the Pr.190 to Pr.196 (output terminal function selection) setting.

The input signal terminal to be used differs according to the Pr.178 to Pr.189 (input terminal function selection) setting.

The AU signal need not be input.
Selection of deviation value, measured value and set point input method,
and PID action method (Pr.128, Pr.609, Pr.610)
• Using Pr.128, select the input method for the PID set point, measured value detected by the meter, and externally
calculated deviation. Also, select forward or reverse action.
• Switch the power voltage/current specifications of terminals 2 and 4 by Pr.73 Analog input selection or Pr.267 Terminal 4
input selection to match the specification of the input device. After changing the Pr.73 and Pr.267 settings, check the
voltage/current input selection switch. Incorrect setting may cause a fault, failure or malfunction. (Refer to
setting.)
Pr.128
Pr.609
PID action
setting
Pr.610
0
PID invalid
10
Reverse action
11
Invalid
Forward action
20
Reverse action
21
Forward action
50
Reverse action
51
Forward action
60
Reverse action
61
Forward action
70
Reverse action
71
Forward action
80
Reverse action
Invalid
81
Forward action
90
Reverse action
91
Forward action
100
Reverse action
101
Forward action
MCCB
R/L1
Power supply
S/L2
T/L3
Forward
STF
rotation
STR
Reverse
rotation
RT(X14)
PID control
selection
SD
10
Setting
Potentiometer
2
(Set point setting)
5
1
4
*4
0 24V
Power
supply
AC1φ
200/220V 50/60Hz
Set point input
Terminal 2 or Pr.133
CC-Link communication
BACnet communication
PLC function
(with frequency reflected)
PLC function
(without frequency
reflected)

(A) Application parameters
Inverter
Motor
U
V
M
W
*3
During PID action
∗2
(PID)SU
Upper limit
(FUP)FU
∗2
∗2
(FDN)OL
Lower limit
Forward rotation
(RL)IPF
∗2
output
Reverse rotation
output
SE
Output signal common
(Measured value) 4 to 20mA
∗1
Measured value input
Terminal 4

,
CC-Link communication

BACnet communication
PLC function
(with frequency reflected)

PLC function
(without frequency
reflected)

Pump
P
2-wire type
3-wire
type
Detector
-
-
+
+
+
(OUT)
(24V)
(COM)
page 306
for the
Deviation input
Terminal 1
CC-Link communication
,

BACnet communication
,

PLC function
(with frequency reflected)

PLC function
(without frequency
reflected)

383
PARAMETERS
5