(T) Multi-Function Input Terminal Parameters
5.9.9

Inverter output shutoff signal

The inverter output can be shut off with the MRS signal. The logic of the MRS signal can also be selected.
Pr.
17
MRS input selection
T720
MRS signal
STF (STR)
signal
(Initial
Setting value "0"
value)
Inverter
Output
stop
MRS
SD (PC)
Assigning a different action for each MRS signal input via
communication and external terminal (Pr.17 = "4")
• When Pr.17 = "4", the MRS signal from an external terminal can be set as the normally closed (NC contact) input, and the
MRS signal from communication as the normally open (NO contact) input. This function is useful to perform operation by
communication with MRS signal from external terminal remained ON.
External MRS
OFF
OFF
ON
ON
NOTE
• The MRS signal is assigned to the terminal MRS in the initial status. By setting "24" in either Pr.178 to Pr.189 (input terminal
function selection), the RT signal can be assigned to the other terminal.
• When using an external terminal to input the MRS signal, the MRS signal shuts off the output in any of the operation modes.
• MRS signal is valid from either of communication or external, but when the MRS signals is to be used as Inverter run enable
signal (X10), it is required to input from external.
• When the terminal assignment is changed using Pr.178 to Pr.189 (input terminal function selection), the terminal name
will be different, which may result in an error of wiring, or affect other functions. Set parameters after confirming the function
of each terminal.
Parameters referred to
???????
Pr.178 to Pr.189 (input terminal function selection)
332
PARAMETERS
Name
Initial value
0
About output shutoff signal (MRS signal)
Motor coasts
to stop
• When the Output stop (MRS) signal is turned ON while operating the
• The response time of the MRS signal is within 2 ms.
• Terminal MRS may be used as described below.
Time
ON
ON
Setting value "2"
Inverter
Output
stop
MRS
MRS signal logic inversion (Pr.17 = "2")
SD (PC)
• When Pr.17 = "2", the MRS signal can be changed to normally closed
Communication MRS
OFF
Operation enabled
ON
Output shutoff
OFF
Output shutoff
ON
Output shutoff
page 329
Setting range
0
2
4
inverter, the inverter output is instantaneously shut off.
(a) To use a mechanical brake (e.g. electromagnetic brake) to stop the
motor
The inverter output is shut off when the mechanical brake operates.
(b) To provide interlock to disable operation by the inverter
With the MRS signal ON, the inverter cannot be operated even if the
start signal is entered into the inverter.
(c) To coast the motor to a stop
When the start signal is turned OFF, the inverter decelerates the
motor to a stop in the preset deceleration time, but when the MRS
signal is turned ON, the motor coasts to a stop.
(NC contact) specification. The inverter will shut off the output with MRS
signal turned ON (opened).
0
Output shutoff
Output shutoff
Output shutoff
Operation enabled
Description
Normally open input
Normally closed input
(NC contact input specification)
External terminal: Normally closed
input (NC contact input specification)
Communication: Normally open input
Pr.17 setting
2
Output shutoff
Output shutoff
Operation enabled
Output shutoff
4