Causes and corrective actions
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
Operation panel
indication
Name
Description
Check point
Corrective action
536
PROTECTIVE FUNCTIONS
Er8
USB memory device operation error
• An operation command was given during the USB memory device operation.
• A copy operation (writing) was performed while the PLC function was in the RUN state.
• A copy operation was attempted for a password locked project.
• Check if the USB memory device is operating.
• Check if the PLC function is in the RUN state.
• Check if the project data is locked with a password.
• Perform the operation after the USB memory device operation is completed.
• Stop the PLC function. (Refer to
• Unlock the password of the project data using FR Configurator2. (Refer to the Instruction Manuals of FR
Configurator2 and GX Works2.)
rE1
Parameter read error
• A failure has occurred at the operation panel side EEPROM while reading the copied parameters.
• A failure has occurred in the USB memory device while copying the parameters or reading the PLC function
project data.
• Perform parameter copy again. (Refer to
• Perform PLC function project data copy again.(Refer to
• The USB memory device may be faulty. Replace the USB memory device.
• The operation panel (FR-DU08) may be faulty. Please contact your sales representative.
rE2
Parameter write error
• Parameter copy from the operation panel to the inverter was attempted during operation.
• A failure has occurred at the operation panel side EEPROM while writing the copied parameters.
• A failure has occurred in the USB memory device while writing the copied parameters or PLC function
project data.
• Check that the inverter is stopped.
• After stopping the operation, perform parameter copy again. (Refer to
• The operation panel (FR-DU08) may be faulty. Please contact your sales representative.
• Perform parameter copy or PLC project data copy again. (Refer to
• The USB memory device may be faulty. Replace the USB memory device.
rE3
Parameter verification error
• The data in the inverter are different from the data in the operation panel.
• A failure has occurred at the operation panel side EEPROM during parameter verification.
• A failure has occurred in the USB memory device during parameter verification.
• The data in the inverter are different from the data in the USB memory device or the personal computer (FR
Configurator2)
• Check the parameter setting of the source inverter against the setting of the destination inverter.
• Continue the verification by pressing
Perform parameter verification again. (Refer to
• The operation panel (FR-DU08) may be faulty. Please contact your sales representative.
• The USB memory device may be faulty. Replace the USB memory device.
• Verify the PLC function project data again.(Refer to
page 433
and the PLC function programming manual.)
————
page
521,
page
524.)
page
433)
.
page
523.)
page
433.)
page
521.)
page 433
and
page
524)