(E) Environment setting parameters
5.4.19

Maintenance timer alarm

The maintenance timer output signal (Y95) is output when the inverter's cumulative energization time reaches the time
period set with the parameter. MT1, MT2 or MT3 is displayed on the operation panel.
This can be used as a guideline for the maintenance time of peripheral devices.
Pr.
503
Maintenance timer 1
E710
504
Maintenance timer 1 warning
E711
output set time
686
Maintenance timer 2
E712
687
Maintenance timer 2 warning
E713
output set time
688
Maintenance timer 3
E714
689
Maintenance timer 3 warning
E715
output set time
First power
9998
(999800h)
Maintenance
timer1
Pr.504
(Pr. 503)
Y95 signal
MT1 display
Operation example of the maintenance timer 1 (Pr.503, Pr.504) (with both MT2 and MT3 OFF)
• The cumulative energization time of the inverter is stored in the EEPROM every hour and displayed in Pr.503 (Pr.686,
Pr.688) in 100 h increments. Pr.503 (Pr.686, Pr.688) is clamped at 9998 (999800 h).
• When the value in Pr.503 (Pr.686, Pr.688) reaches the time (100 h increments) set in Pr.504 (Pr.687, Pr.689), Maintenance
timer signal (Y95) is output, and also
• For the terminal used for Y95 signal output, assign the function by setting "95 (positive logic)" or "195 (negative logic)" in
any of Pr.190 to Pr.196 (output terminal function selection).
NOTE
• The Y95 signal turns ON when any of MT1, MT2 or MT3 is activated. It does not turn OFF unless all of MT1, MT2 and MT3
are cleared.
• If all of MT1, MT2 and MT3 are activated, they are displayed in the priority of "MT1 > MT2 > MT3".
• MT is displayed on the FR-PU07 parameter unit if any of MT1, MT2 or MT3 is activated.
• The cumulative energization time is counted every hour. Energization time of less than 1 h is not counted.
• Changing the terminal assignment using Pr.190 to Pr.196 (output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
???????
Pr.190 to Pr.196 (output terminal function selection)
184
PARAMETERS
Name
Initial value
0
9999
0
9999
0
9999
ON
Set "0" in Pr.503
OFF
ON
(MT1),
page 288
Setting range
0(1 to 9998)
0 to 9998
9999
0(1 to 9998)
0 to 9998
9999
0(1 to 9998)
0 to 9998
9999
Time
ON
(MT2), or
Description
Displays the inverter's cumulative
energization time in increments of 100 h
(read-only).
Writing the setting of "0" clears the
cumulative energization time while
Pr.503 = "1 to 9998". (Writing is disabled
when Pr.503 = "0".)
Set the time until the maintenance timer
signal (Y95) is output.
MT1 is displayed on the operation panel.
No function
The same function as Pr.503.
The same function as Pr.504.
MT2 is displayed on the operation panel.
The same function as Pr.503.
The same function as Pr.504.
MT3 is displayed on the operation panel.
(MT3) is displayed on the operation panel.