(A) Application parameters
5.11.12

Offline auto tuning for a frequency search

V/F
V/F
V/F
During V/F control or when driving the IPM motor MM-EFS/MM-THE4, the accuracy of the "frequency search", which is
used to detect the motor speed for the automatic restart after instantaneous power failure and flying start, can be
improved.
Pr.
Name
Automatic restart after
162
instantaneous power failure
A700
selection
298
Frequency search gain
A711
560
Second frequency search
A712
gain
96
Auto tuning setting/status
C110
90
Motor constant (R1)
C120
463
Second motor auto tuning
C210
setting/status
458
Second motor constant (R1)
C220

For the FR-F820-02330(55K) or lower and FR-F840-01160(55K) or lower.

For the FR-F820-03160(75K) or higher and FR-F840-01800(75K) or higher.
422
PARAMETERS
PM
PM
PM
Initial
value
0 (2)
1
3
0
10 (12)
11
13
0 to 32767
9999
9999
0 to 32767
9999
9999
0
1, 101
0
11
0 to 50 Ω, 9999
9999
0 to 400 mΩ, 9999
0
1, 101
0
11
0 to 50 Ω, 9999
9999
0 to 400 mΩ, 9999
Setting range
Frequency search only performed at the first start
Reduced voltage start only at the first start
(no frequency search)
Frequency search only performed at the first start
(reduced impact restart)
Frequency search at every start
Reduced voltage start at every start (no frequency
search)
Frequency search at every start (reduced impact
restart)
The offline auto tuning automatically sets the gain
required for the frequency search.
Uses the constant value of Mitsubishi motor (SF-PR,
SF-JR, SF-HR, SF-JRCA, SF-HRCA, MM-EFS, MM-
THE4 and so on).
The offline auto tuning automatically sets the gain
required for the frequency search of the second
motor.
Uses the constant value of Mitsubishi motor (SF-PR,
SF-JR, SF-HR, SF-JRCA, SF-HRCA, MM-EFS, MM-
THE4 and so on).
No offline auto tuning.
Perform offline auto tuning for the Advanced
magnetic flux vector control. (Refer to
Performs offline auto tuning without rotating the motor
(V/F control, PM motor control (IPM motor MM-EFS/
MM-THE4)).
Tuning data

(The value measured by offline auto tuning is
automatically set.)
9999: Uses the constant value of Mitsubishi motor

(SF-PR, SF-JR, SF-HR, SF-JRCA, SF-HRCA and so
on).
No auto tuning for the second motor.
Performs offline auto tuning for the second motor.
Performs offline auto tuning without rotating the
second motor (V/F control, PM motor control (IPM
motor MM-EFS/MM-THE4)).

Tuning data of the second motor
(same as Pr.90)

Description
page
341.)

Hide quick links: