Adjusting The Response Of Input Terminal (Pr.699) - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

NOTE
• Same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
• Priority of the speed command is JOG > multi-speed setting (RH, RM, RL, REX) > PID (X14).
• When the (X10) signal is not set up, Pr.79 Operation mode selection = "7", and PU operation external interlock (X12) signal
is Inverter run enable signal.
• Same signal is used to assign multi-speed (7 speed) and remote setting. Setting cannot be performed individually.
• When the terminal assignment is changed using Pr.178 to Pr.189 (input terminal function selection), the terminal name
will be different, which may result in an error of wiring, or affect other functions. Set parameters after confirming the function
of each terminal.
Adjusting the response of input terminal (Pr.699)
• Response of the input terminal can be delayed in a range between 5 to 50 ms. (Example of STF signal operation)
ON
STF
Pr.699
9999
Pr.699
NOTE
• Setting of Pr.699 is disabled (no filter) in the following cases.
- Input terminal is already turned ON when the power is turned ON
- Input signal used for the PLC function
- Inverter run enable signal (X10) signal
(T) Multi-Function Input Terminal Parameters
Time
OFF
Pr.699
331
PARAMETERS