To run with an analog input voltage
Inverter
• Concerning the frequency setting signal, input 0 to 5 VDC (or 0 to 10 VDC) to
Voltage/current
terminals 2 and 5. The 5 V (10 V) input is the maximum output frequency.
input switch
• The power supply 5 V (10 V) can be input by either using the internal power
supply or preparing an external power supply. The internal power source is 5
VDC output between terminals 10 and 5, and 10 VDC output between
2
4
terminals 10E and 5.
Terminal
Inverter
10
Voltage/current
input switch
10E
• To supply the 10 VDC input to terminal 2, set "0, 2, 4, 10, 12, or 14" in Pr.73.
(The initial value is 0 to 5 V.)
2
4
• Setting "1 (0 to 5 VDC)" or "2 (0 to 10 VDC)" in Pr.267 and turning the voltage/
current input switches OFF sets the terminal 4 to the voltage input
specification. Turning ON the AU signal activates terminal 4 input.
Inverter
STF
Voltage/current
AU
input switch
SD
10
4
2
4
5
Inverter internal
power source
voltage
5 VDC
10 VDC
NOTE
• The wiring length of the terminal 10, 2, 5 should be 30 m at maximum.
Frequency
setting
(terminal 2
resolution
input voltage)
0.030 Hz/60 Hz
0 to 5 VDC input
0.015 Hz/60 Hz
0 to 10 VDC input
Pr.73