Setting multiple PID pre-charge functions
• When the second pre-charge function is set, two sets of pre-charge functions can be switched for use. The second pre-
charge function is enabled by turning ON the RT signal.
• The second pre-charge function parameters and signals function in the same way as the following parameters and signals
of the first pre-charge function. Refer to the first pre-charge function when setting the second pre-charge functions.
First pre-charge function parameters
Classification
Pr.
760
761
762
Parameter
763
764
1132
First pre-charge function parameters
Classification
Signal
Input signal
X77
Y49
Output signal
Y51
Y53
NOTE
• The second PID pre-charge function is valid also when the first pre-charge function is set to invalid and the second pre-
charge function is set.
• When "10" (second function enabled only during constant-speed operation) is set to Pr.155, the second PID function is not
selected even if the RT signal turns ON.
Ending level
Pr.764
E.PCH
Name
Pre-charge fault selection
Pre-charge ending level
Pre-charge ending time
Pre-charge upper detection level
Pre-charge time limit
Pre-charge change increment amount
Name
Pre-charge end command
During pre-charge operation
Pre-charge time over
Pre-charge level over
When Pr.760="0",
output is immediately shut off.
E.PCH
When Pr.760="1",
output is shut off after the motor decelerates to a stop.
Second pre-charge function parameters
Pr.
765
Second pre-charge fault selection
766
Second pre-charge ending level
767
Second pre-charge ending time
Second pre-charge upper detection
768
level
769
Second pre-charge time limit
Second pre-charge change increment
1133
amount
Second pre-charge function parameters
Signal
X78
Second pre-charge end command
Y50
During second pre-charge operation
Y52
Second pre-charge time over
Y54
Second pre-charge level over
(A) Application parameters
Time
Time
Time
Time