Selection of control source in Network operation mode (Pr.338, Pr.339)
• There are two control sources: the start command source, which controls the signals related to the inverter stand command
and function selection, and the speed command source, which controls signals related to frequency setting.
• The table below shows the commands from the external terminals and communication (RS-485 terminals or
communication option) in the Network operation mode.
Pr.338 Communication
Operation
operation command source
location
Pr.339 Communication speed
selection
command source
Running frequency from
Fixed function
communication
(terminal-
Terminal 2
equivalent
Terminal 4
function)
Terminal 1
Low-speed operation
command/remote setting
0
RL
Clear/Stop-on-contact
selection 0
Middle-speed operation
1
RM
command/remote setting
deceleration
High-speed operation
2
RH
command/remote
setting acceleration
Second function selection/
3
RT
stop-on-contact selection 1
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
6
CS
No function
7
OH
External thermal relay input
8
REX
15-speed selection
10
X10
Inverter run enable signal
FR-HC2/FR-CC2 connection,
11
X11
instantaneous power failure
detection
PU operation external
12
X12
interlock
External DC injection brake
13
X13
operation start
14
X14
PID control valid terminal
PU/External operation
16
X16
switchover
18
X18
V/F switchover
Output stop
24
MRS
PU operation interlock
STP
25
Start self-holding selection
(STOP)
Start-time tuning start
28
X28
external input
37
X37
Traverse function selection
PID multistage set point
38
PDI1
setting 1
PID multistage set point
39
PDI2
setting 2
PID multistage set point
40
PDI3
setting 3
46
TRG
Trace trigger input
47
TRC
Trace sampling start/end
48
X48
Power failure stop external
(D) Operation command and frequency command
0: NET
0:
2:
1: EXT
NET
EXT
NET
NET
―
NET
NET
―
External
―
―
―
External
―
Compensation
NET
External
NET
NET
External
NET
NET
External
NET
NET
External
―
Combined
―
―
External
External
External
NET
External
NET
External
External
External
NET
External
NET
External
NET
External
NET
External
Combined
External
External
-
External
NET
External
NET
External
NET
External
NET
NET
External
NET
NET
External
NET
NET
External
NET
External
External
1: EXT
REMARKS
0:
1:
2:
EXT
EXT
―
NET
―
―
External
External
Pr.59 ="0" (multi-
speed)
Pr.59 "0" (remote)
External
Pr.270 ="1, 3, 11, or
13" (stop-on-contact)
External
Pr.270 ="1, 3, 11, or
13" (stop-on-contact)
Combined
Pr.59 ="0" (multi-
External
speed)
External
Pr.79 ≠ "7"
Pr.79 = "7"
When X12 signal is
not assigned.
External
External
External
PARAMETERS
5
GROUP
D
215