Selection of control source in Network operation mode (Pr.338, Pr.339)
• There are two control sources: the start command source, which controls the signals related to the inverter stand command
and function selection, and the speed command source, which controls signals related to frequency setting.
• The table below shows the commands from the external terminals and communication (RS-485 terminals or
communication option) in the Network operation mode.
Pr.338 Communication
Operation
operation command source
location
Pr.339 Communication speed
selection
command source
Running frequency from
Fixed function
communication
(terminal-
Terminal 2
equivalent
Terminal 4
function)
Terminal 1
Low-speed operation
command/remote setting
0
RL
Clear/Stop-on-contact
selection 0
Middle-speed operation
1
RM
command/remote setting
deceleration
High-speed operation
2
RH
command/remote
setting acceleration
Second function selection/
3
RT
stop-on-contact selection 1
4
AU
Terminal 4 input selection
5
JOG
Jog operation selection
6
CS
No function
7
OH
External thermal relay input
8
REX
15-speed selection
10
X10
Inverter run enable signal
FR-HC2/FR-CC2 connection,
11
X11
instantaneous power failure
detection
PU operation external
12
X12
interlock
External DC injection brake
13
X13
operation start
14
X14
PID control valid terminal
PU/External operation
16
X16
switchover
18
X18
V/F switchover
Output stop
24
MRS
PU operation interlock
STP
25
Start self-holding selection
(STOP)
Start-time tuning start
28
X28
external input
37
X37
Traverse function selection
PID multistage set point
38
PDI1
setting 1
PID multistage set point
39
PDI2
setting 2
PID multistage set point
40
PDI3
setting 3
46
TRG
Trace trigger input
47
TRC
Trace sampling start/end
48
X48
Power failure stop external
(D) Operation command and frequency command
0: NET
0:
2:
1: EXT
NET
EXT
NET
NET
NET
NET
External
External
Compensation
NET
External
NET
NET
External
NET
NET
External
NET
NET
External
Combined
External
External
External
NET
External
NET
External
External
External
NET
External
NET
External
NET
External
NET
External
Combined
External
External
-
External
NET
External
NET
External
NET
External
NET
NET
External
NET
NET
External
NET
NET
External
NET
External
External
1: EXT
REMARKS
0:
1:
2:
EXT
EXT
NET
External
External
Pr.59 ="0" (multi-
speed)
Pr.59 "0" (remote)
External
Pr.270 ="1, 3, 11, or
13" (stop-on-contact)
External
Pr.270 ="1, 3, 11, or
13" (stop-on-contact)
Combined
Pr.59 ="0" (multi-
External
speed)
External
Pr.79 ≠ "7"
Pr.79 = "7"
When X12 signal is
not assigned.
External
External
External
PARAMETERS
5
GROUP
D
215