Load Characteristics Fault Detection - Mitsubishi Electric FR-F800 Instruction Manual

Hide thumbs Also See for FR-F800:
Table of Contents

Advertisement

5.7.12

Load characteristics fault detection

This function is used to monitor whether the load is operating in normal condition by storing the speed/torque
relationship in the inverter to detect mechanical faults or for maintenance. When the load operating condition is
deviated from the normal range, the protective function is activated or the warning is output to protect the inverter or the
motor.
Pr.
Name
1480
Load characteristics
H520
measurement mode
1481
Load characteristics load
H521
reference 1
1482
Load characteristics load
H522
reference 2
1483
Load characteristics load
H523
reference 3
1484
Load characteristics load
H524
reference 4
1485
Load characteristics load
H525
reference 5
1486
Load characteristics
H526
maximum frequency
1487
Load characteristics
H527
minimum frequency
1488
Upper limit warning
H530
detection width
1489
Lower limit warning
H531
detection width
1490
Upper limit fault
H532
detection width
1491
Lower limit fault
H533
detection width
Load status detection
1492
signal delay time / load
H534
reference measurement
waiting time
Initial value
Setting
range
FM
CA
0
1
0
2, 3, 4, 5, 81,
82, 83, 84, 85
9999
9999
9999
0 to 400%
9999
9999
60 Hz 50 Hz 0 to 590 Hz
6 Hz
0 to 590 Hz
0 to 400%
20%
9999
0 to 400%
20%
9999
0 to 400%
9999
9999
0 to 400%
9999
9999
1 s
0 to 60 s
(H) Protective function parameter
Description
Load characteristics measurement is normally completed.
Load characteristics measurement mode is started.
The load characteristics measurement status is displayed.
(Read-only)
Set the reference value of normal load characteristics.
8888: The present load status is written as reference status.
9999: The load reference is invalid.
Set the maximum frequency of the load characteristics fault
detection range.
Set the minimum frequency of the load characteristics fault
detection range.
Set the detection width when the upper limit warning is output
for load faults.
Function disabled
Set the detection width when the lower limit warning is output
for load faults.
Function disabled
Set the detection width when output is shut off when the upper
limit load fault occurs.
Function disabled
Set the detection width when output is shut off when the lower
limit load fault occurs.
Function disabled
Set the waiting time after the load fault is detected until
warning output or output shutoff.
In the load characteristics measurement mode, set the waiting
time after the load measurement frequency is reached until the
load reference is set.
PARAMETERS
5
GROUP
H
255